Page 42 of 83
SK2018 PCG(H)-V/P-AECM-001
C.6.
Motor and Fan Blower Replacement
Refer to Section C.5. for Steps 1, 2 and 3.
Step 4: Use a spanner to remove the fan blower.
Step 5: Remove motor by undoing the 4 bolts.
Disconnect wire connector and replace the motor.
C.7.
Condensate Pump Kit Replacement
Refer to Section C.5. for Steps 1, 2 and 3.
Step 4: Remove front panel and disconnect
stepping motor and IR receiver.
Step 5: Unscrewing the 8 screws as shown
above.
Step 6: Remove the drain pan and internal drain
pan.
Step 7: Remove the pump kit (including Drain
pump and Float switch) and replace it.
Wire connector
Mounting
bolt