Page 61 of 83
SK2018 PCG(H)-V/P-AECM-001
If Tr
≧
41ºF for 2 minutes
1.
MTV1 is turned OFF
2.
AUX1 is open
3.
DA2 is 0 VDC
4.
Electric Heater is turned OFF
5.
Indoor fan Switched OFF
If Unit with SW2=1(4-pipe system), is in Standby Mode
If Tr
≦
35.6 ºF for 2 minutes
1. MTV2 is turned ON
2. AUX1 is closed
3. DA3 is 10 VDC
4. If Ti2 < 41ºF for 2 minutes EH (if present) is switched ON
5. Indoor fan is turned on at low speed
If Tr
≧
41ºF for 2 minutes
1.
MTV2 is OFF
2.
AUX1 is open
3.
DA3 is 0 VDC
4.
Electric Heater is turned OFF
5.
Indoor fan Switched OFF