USE OM - JANUARY 2017
36
ICM or Systems Manufacturer Test Failure Options
Test Efficiency < NAECA or EPACT Minimum
Is this First
Sample Test?
Tested Combination is
Obsoleted and Tested
Ratings are Shown
Participant
Elects to Test
Additional
Samples?
See Test
Additional
Samples
Process
Yes
Yes
No
No
Is Tested
Combination
HSVTC?
All Combinations within
the BMG are Rerated by
the % by which the
Tested System Failed
Yes
Rerated
Combination >
Applicable
Minimum?
Complete
Yes
Rerated Combination is
Obsoleted and Rerated
Values are Shown
No
Single Combination can be
Tested to Restore Ratings
for that Combination
Is HSVTC Test
Requested?
No
HSVTC is Tested for
BMG
Yes
HSVTC Test
Pass?
All Combinations within the BMG
are Rerated by the % by which
the Tested System Failed, Except
the HSVTC Combination
Rerated
Combination >
Applicable
Minimum?
Complete
Yes
Rerated Combination is
Obsoleted and Rerated
Values are Shown
Single Combination can be
Tested to Restore Ratings
for that Combination
No
Yes
Test Failure of
HSVTC Follow OM
Procedures
See First
Test Failure
Options
No
Test Efficiency < NAECA or EPACT Minimum
Figure D7: ICM or System Manufacturer First or Additional Sample Failure Options