Power Quality Analyzer PowerPad
®
IV Model 8345
45
Disconnecting the instrument from the network:
1. Disconnect in the reverse order of connection and always end by
disconnecting the earth, neutral, or both.
2. Disconnect the leads from the instrument.
4.5 INSTRUMENT FUNCTIONS
4.5.1 Measurements
There are 4 possible real-time modes: waveform
, harmonics
, power
, and energy
There are 5 possible recording modes: trend
, transients
, inrush
currents
, alarms
, and network monitoring
1.
Ensure that the instrument’s configuration is correct for the desired
measurements.
2. Then, you can make the following measurements:
• View a signal’s waveforms
• View a signal’s harmonics
• View power measurements
• Meter energy
• Record a trend
• Record transients
• Capture an inrush current
• Detect alarms
• Monitor a network
Some functions cannot be run simultaneously:
■
The real-time modes (waveform, harmonics, power, and energy) can be
activated while recordings are in progress
■
If an inrush current capture is in progress, you cannot start the recording of
a trend, transients, alarms, or monitoring
■
If a recording of a trend, transients, alarms, or monitoring is in progress, you
cannot start an inrush current capture
4.5.2 Screenshot
1. To record a screenshot, hold the
button, or click on the icon in the
status bar.
2. Release the
button or icon when the symbol turns black . If
you release the button or icon before the symbol turns black, no screenshot
will be recorded.
The screenshots are recorded on the SD card in directory 8345\Photograph
Real-time screens that vary, like curves or metering, are captured in bursts of up
to 5 snapshots, so you can choose the best screenshot for your needs