Chapter 3 — Measuring with the DWR-10
September 2004
Page 45
Changing Windings and Testing Taps
Changing Winding Connections
If you need to change the winding connections:
1. Press
the
Test/Dump
button to interrupt the current
injection.
2. Change the winding connections.
3. Update the winding names in the
Unit Definition
window.
4. Press
the
Test/Dump
button again to take new
readings.
This can be repeated as many times as necessary, until
you press the
End & Record Session
button on the
default toolbar to save the manual file.
Testing Tap with On-load Tap Changer
To test a tap on a transformer with an on-load tap changer
(LTC), you must first connect the DWR-10 to the tap
changer control circuit.
1. Review the tap changer control drawings and connect
the DWR-10's tap changer leads to appropriate points
in the control circuit.
2. Ensure that the voltage and current at these points do
not exceed the ratings of the DWR contacts.
3. Ensure the current is on.
4. Raise or lower the taps by pressing the
Tap Changer
button through the range.
5. Edit
the
Tap
field.