Chapter 3 — Measuring with the DWR-10
September 2004
Page 43
2. Accept or change the interval, anywhere from 5 to
100 seconds. The default is 15 seconds. A 15-second
interval means the DWR-10 will perform a winding
resistance test every 15 seconds, automatically. (Your
chosen time interval will be displayed in the main
status panel.)
3. Press
the
Menu
button again and open the
Unit
Definition
window.
4. Enter the serial number of the transformer (if not
already entered) and other data, as desired.
5. Press
the
Back
button.
6. Press
the
Tap/Winding
button and enter tap and
winding information.
7. At the same time, disconnect the AC source that is
injecting the power transformer
and
press the
Clock
On/Off
button (the measurement duration is recorded
in the
Total Time
field on the main window).
8. Connect the test leads to the transformer windings.
9. Press
the
Test/Dump
button to apply current.
10. When readings are stable, press the
Auto On/Off
button to start automatic recording of time and
resistance (the countdown is recorded in the
Next
Meas
. field on the main window).