Chapter 3 — Measuring with the DWR-10
September 2004
Page 39
6. Repeat the above steps for the B-channel.
7. Press
the
Back
button to exit.
Test Modes
There are two modes of operation:
Manual
and
Timed
.
In
Manual
mode, you can manually take and record
measurements one at a time. There are two manual
methods:
•
Testing without saving
— Perform a fast test
without saving any results or data.
•
Testing and saving
— Save all measured results, tap
and winding details, and details about the transformer
and its location. You can also produce reports that
include all saved data.
In
Timed
mode, measurements can be taken
automatically at set intervals (or manually), and the date
and time of the winding resistance measurement is also
recorded. Measurements are saved in a single file, as
opposed to multiple files for
Manual
mode. The
Timed
mode is an optional feature that only comes with the 'T'
version of the DWR-10. It is normally only used by
transformer manufacturers who must record time data at
the end of a heat run to calculate hot resistance.
Testing in Manual Mode
To test in
Manual
mode:
1. Decide if you want to test and save the results to a
file in the memory of the DWR-10, or if you want to
test without saving.