Chapter 3 — Measuring with the DWR-10
Page 40
September 2004
2. Decide if you want to test one winding at a time, or
two windings in series. (To test two in series, see the
instructions above.)
3. Connect the test leads to the transformer.
4. Select
Manual
mode from the menu list.
Testing Without Saving
Use this method if you want to test without saving results
and data.
1. Press
the
Test/Dump
button to start the current
injection.
2. Press
the
Test/Dump
button again when you are
finished. The current indicator will turn red
indicating the current is discharging.
3. Do not disconnect the test leads until the reading
becomes zero.
Testing and Saving
Use this method if you want to save results and
transformer data to a file for future printing or report
production.
1. Press
the
Menu
button and open the
Unit Definition
window.
2. Enter the serial number of the transformer.
3. Enter other data as required in the
Unit Definition
window (optional).
4. Press
the
Back
button.
5. If required, press the
Tap/Winding
button to enter
tap and winding information.