Table 3‑10. Fan current, air volume, and sound pressure (Continued)
Model
Current (A)
Air Volume
(m
3
/h)
Sound Pressure
(dbA @ 1m)
50 Hz 60 Hz
300 HF, 350 HF,
495 HF, 500 HF,
650 HF
0.50
0.38
230
67
780 HF, 1000 HF,
1400 HF, 1500 HF
1.00
1.20
1200
81
1850 HF, 2000 HF,
2400 HF, 2750 HF
1.00
1.20
2100
81
3PX and 1PX ... VSC 3
200 HF, 280 HF
0.50
0.38
260
67
300 HF, 350 HF,
495 HF, 500 HF,
650 HF
1.20
0.85
450
72
780 HF, 1000 HF,
1400 HF, 1500 HF
1.00
1.20
1600
81
1700 HF, 1850 HF,
2200 HF, 2600 HF
1.00
1.20
2000
81
Fans for HF units must be running when the unit is operating. Connect the fans
according to connecting diagrams. When operating conditions are below +10°C
(50°F), a longer fan startup time is required. Therefore, the overcurrent protection
device should be rated at twice the specified continuous current.
ENVIRONMENTAL SPECIFICATIONS
The two following tables describe the environmental specifications for the Thyro-PX
unit.
Table 3‑11. Environmental standard specifications
Description
Specification
Overvoltage
Category II
Pollution degree
2