Table 3‑4. Electrical specifications (Continued)
Description
Specification
Precision
U-control: Better than ± 0.5%
I-control: Better than ± 0.5%
P-control: Better than ± 1%
All specifications are relating to the respective final value.
Limitations
Voltage limitation U
rms
Current limitation I
rms
= default setting
Effective power limitation P
Peak current limitation, MOSI starting mode
Relays
Rated current: 6 A
Rated voltage: 250 VAC
Rated load AC1: 1500 VA
Breaking capacity DC1: 30 V/6 A, 110 V/0.2 A, 220 V/0.12 A
Minimum switching load: 500 mW (12 V/10 mA)
Contact material: AgNi+Au
Table 3‑5. Type Voltage 500 Volts
Model
Type Current
(A)
Type Power
(kVA)
Dissipation
(W)
Current
Transformer
T1
Burden
R (Ω)
Fuse F1
(A)
Thyro-PX 1PX
16 H
8
71
400/1
27.4
50
37 H
18
105
100/1
2.7
50
75 H
38
130
100/1
1.30
100
110 H
55
175
100/1
0.91
180
130 H
65
190
150/1
1.10
200
170 H
85
220
200/1
1.10
315
280 HF
140
365
300/1
1.00
350
350 HF
175
477
500/1
1.30
500
495 HF
248
595
500/1
1.00
630
650 HF
325
750
700/1
1.00
900
1000 HF
500
1450
1000/1
1.00
2x1000
1500 HF
750
1775
1500/1
1.00
4x900
2100 HF
1050
2600
2000/1
0.91
1x1000
2900 HF
1450
3400
3000/1
1.00
4x1500
Advanced Energy
®
Thyro-PX® Power Controller
57010148-00B
Specifications
3‑5