Setpoint configuration
Remote
Total setpoint
Motor potentiometer
Addition
Analog setpoint
Bus setpoint
Setpoint configuration
Local
Motor potentiometer
Addition
Analog setpoint
Bus setpoint
Remote/local switch
Figure 5‑35. Total setpoint
The local analog setpoint, and local motor potentiometer setpoint are used by default.
If an Anybus module is installed, the remote bus setpoint is used by default.
Switching between the local setpoint and the remote setpoint can be controlled using
the Thyro-Touch display, the Thyro-Tool Pro PC software, or the bus
communication. A digital I/O line may also be configured to control the local/remote
switch.
Table 5‑4. Setpoint characteristics
Input Type
Input Characteristics
0 mA to 20 mA
4 mA to 20 mA
Ri = ca. 250 Ω / max. 24 mA
Do not exceed 12 V open-
circuit
0 V to 5 V
1 V to 5 V
Ri = ca. 6.6 kΩ / max. 12 V
0 V to 10 V
2 V to 10 V
Ri = ca. 11.1 kΩ / max. 12 V
Advanced Energy
®
Thyro-PX® Power Controller
57010148-00B
Installation, Setup, and Operation
5‑34