39
Accord xpC - July, 2001
Group 0 — Option 3 Assistance Channel
The engineer can assign any zone as an Assistance Channel. This option when enabled
will overide any chosen Group 8 Option.
0.
Disabled
1.
Overide report Fire to ARC
2.
Overide report PA channel to ARC
3.
Overide report Alarm channel to ARC
4.
Overide report Set/Unset channel to ARC
5.
Overide report Day Tamper channel to ARC
6.
Overide report RF Low Battery channel to ARC
7.
Overide report Abort channel to ARC
8
Overide report Verify Alarm channel to ARC
This option defaults to 6.
Note: The function of Assistance Channel depends upon the relevant Group 8 Option
being enabled.
Zone Type Definitions
General Information
The Accord xpC has ten zone types, these are:
0 — Not Used
Zones which are unused should be programmed as 0 Not Used. These zones should also
be linked out using the appropriate zone link or 1K resistor provided in the Auxilliary
pack.
1 — Final Exit
The Final Exit zone is used for the entry/exit route(s), usually assigned to the front door
or other main entry point(s). The zone becomes operational when the system is set or
setting.
The Exit Time must be set to infinite (410) for a Final Exit zone to terminate a Full
Setting procedure.
Activation of a Final Exit zone while the system is set, initiates the unsetting procedure.
The keypads beep and all Intermediate Exit Zones are isolated. A valid User Code must
be entered at the keypad or a Keyswitch Zone activated before the Entry Time has elapsed.
The Exit Time is fixed at 30 seconds when the system is Part Set or Night Set then.