EN
WMBus Smart Building MOTION - Guide utilisateur / User guide version V1.0.0
59
Page
of 82
FR
Eg:
Register
Value code Value
Result
S382
Hexadecimal 0x41
Configuration of the Digital Input 2
input (terminal block):
• Detection of high edges
• Debounce time* 100ms
S383
Decimal
5
The device sends a frame every 5
times that a high edge is detected on
Digital Input 2
* Debounce time: minimum time to take account of a change of state. For example, if this period is
10 ms all pulses (high or low level) whose duration is less than 10 ms will not be considered. This
technique avoids potential rebounds during a change of state.
In this example the device:
• The device has a debounce time of 100 ms and the button press alarm is enabled (register
383).
• The device sends a frame as soon as it has detected 5 high edges on its digital input per
terminal block (register S382)
The digital input operates only in event mode (no periodic sending).
2.2. Operation of the LEDs
Mode
LED red state
LED green state
Device in Park/Storage mode
OFF
OFF
Long button press (2 seconds) in PARK mode
-
ON when you press button for 1 second
Starting the device (after detecting long
button press)
-
Fast flashing 6 cycles 100 ms ON / 100 ms
OFF
Switching to command mode
Continuously lit*
Continuously lit*
Low battery level
Flashing (500ms ON every 60s)
-
Device in default (return to factory)
Fixed
-
Button press in OPERATING mode
ON for 500 ms *
ON for 500 ms *
Presence detection
ON for 500 ms *
ON for 500 ms *
Device in REPLI mode
Flashing (100ms ON / 100ms OFF) x2 every
5s
-
* The green and red LED lights simultaneously give a white/yellow rendering through the case.
NOTE: It is possible to program the sending of a frame only after a certain number of edge detections (S381/S383).
Product in standby
Send frame 0x51 or
0x52
State
change
on digital
input(s)?
Oui
Non
Number of
occurrences
reached?
Non