CHAPTER 4
Sensor Type Configuration
207
Figure 233. Sensor type - Conversion settings - Sensor table - SDI
Note: If a sensor table is entered for a non-linear sensor, the fol-
lowing entries for Linear input value refer to the output val-
ues of the linearization table and not to the voltage
measured on the analog pin!
•
Linear input value - entry of the minimum and maximum value
of the range within which the sensor delivers measurements;
Note: Due to its linear characteristic, a linear sensor is by default
exactly defined by only two input values, the minimum and
the maximum. The range for SDI sensors is 0 - 1 Units, by
default.
•
Linear output value - entry of the minimum and maximum
value of the linear output range which has to correspond to
the linear input value range, in the engineering units which
have been selected;
•
Verifier - entry of the minimum and maximum value within
which valid sensor measurement results can be expected. If
the values are outside the preset thresholds, an invalid sensor
value will be notified;
•
Display scale - enter the minimum and maximum value for
scaling which should to be displayed on the trend graph
“Sensor data graphic”.
Combo Sensor Types
A combo sensor type consists of several (at least two) “normal”
sensors and may have its own name, manufacturer and subclass
(i.e., the name of each individual sensor type within the combo
sensor). For example, an sensor of type “SEN-R” for binder type
connectors provides a temperature sensor which uses pin 1 and a
relative humidity sensor which uses pin 2; thus, this combo sensor
Содержание A850
Страница 92: ...CHAPTER 3 Configuring the Gateway 92 Figure 81 PPP Configuration Window ...
Страница 107: ...CHAPTER 3 107 Figure 101 SSH Tunnel Window The following window areas are available through the SSH tun nel window ...
Страница 128: ...CHAPTER 3 Configuring the Gateway 128 Figure 132 Dialup Modem Window ...
Страница 164: ...CHAPTER 3 Configuring the Gateway 164 ...
Страница 177: ...CHAPTER 4 Sensor Type Configuration 177 Figure 183 Sensor type Window Analog ...
Страница 196: ...CHAPTER 4 Using the Gateway 196 Figure 216 Sensor type Window LC ...
Страница 200: ...CHAPTER 4 Using the Gateway 200 Figure 222 Sensor type Window OC ...
Страница 204: ...CHAPTER 4 Using the Gateway 204 Figure 228 Sensor type Window SDI ...
Страница 215: ...CHAPTER 4 Logs 215 Figure 241 System Log Selection Log types Figure 242 System Log Log types ...
Страница 275: ...CHAPTER 4 RTU Network Configuration 275 Sensor details Figure 319 Sensor details Window ...
Страница 366: ...CHAPTER 6 Appendix 366 ...