For a 0°C to 50°C (32°F to 122°F) operating environment, a fan assembly is required for any of these situations:
•
One system with
≥
230W power dissipation
•
Four systems with
≥
948W power dissipation
•
Extended temperature operation (65°C or 149°F)
No shelf configuration should exceed a total power dissipation
≥
1275W.