Installation and Commissioning Guide
Advance Outdoor Units
Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
51
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
EVV210S / EFV210S
NOTES
* Only applicable to Third Party controllers
W = Indoor Fan Power, Watts
PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the LR7-1, LC7-2, NEO or Outdoor Board).
Default Fan Speed Value at 100 Pa
Speed
Default PWM (adjustable)
Indoor Fan PWM Limits
High PWM (%)
82
High PWM Limit
99
Medium PWM (%)
61
Low PWM Limit
38
Low PWM (%)
43
APPLICATION RANGE (COMPRESSOR ON) *
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
810
38
192
43
266
49
333
54
408
59
484
70
561
850
41
214
46
279
51
349
57
437
62
511
74
592
900
45
244
50
313
56
397
61
473
66
548
80
634
950
49
275
54
343
60
431
65
508
71
599
87
688
1000
53
304
59
388
64
464
70
561
75
652
93
739
1020
55
321
61
407
66
485
71
574
77
666
1050
58
347
64
436
69
515
73
593
81
694
1100
63
391
68
467
73
561
79
657
88
750
1150
68
435
73
527
78
608
84
705
96
817
1200
72
472
78
571
84
666
90
774
1230
75
501
82
608
88
710
93
810
MOTOR / BLOWER UNIT