Installation and Commissioning Guide
Advance Outdoor Units
Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
13
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
CRV160S / CRV160T / CRV180S / CRV180T
FRONT VIEW
TOP VIEW
SIDE VIEW
** DRAWING IS SUBJECT TO CHANGE WITHOUT NOTICE**
CONDENSATION POINTS ARE DESIGNED TO ENSURE ALL
CONDENSATION IS REMOVED EFFICIENTLY TO AVOID
WATER POOLING WITHIN THE CONDENSER. IF A SINGLE
CONDENSATION DRAIN POINT IS REQUIRED, ACTRONAIR
RECOMMENDS THE INSTALLATION OF A CONDENSER
TRAY. THESE ARE AVAILABLE AS AN ADDITIONAL
ACCESSORY.
UNIT MODEL
NUMBER
UNIT WEIGHT
(kg)
CORNER WEIGHTS (kg)
A
B
C
D
CRV160S
144
22
36
34
52
CRV160T
150
22
41
34
53
CRV180S
152
22
43
34
53
CRV180T
155
23
44
35
53
ACCESS
PANEL
OUTDOOR COIL
COMP
1460 O/A
580
O/A
255
1045
O/A
585
980
517
(MTG C-C DIST)
1003
1118
(MTG C-C DIST)
56
110
115
57.5
30
35
25
25
OUTDOOR
AIR INLET
OUTDOOR AIR INLET
OUTDOOR
AIR INLET
OUTDOOR
AIR INLET
ELECT. ACCESS
2 x Ø 25.4mm (1")
LIQUID PIPE
Ø 9.52mm (3/8")
SWAGED
340
500
115
CONDENSATION
POINTS
CONDENSATION
POINTS
115
GAS PIPE
Ø 19.05mm (3/4")
SWAGED
D
300 mm
SERVICE /
AIRFLOW
CLEARANCE
600 mm
SERVICE
CLEARANCE
(COMPRESSOR
AND
ELECTRICALS)
NIL - TO - MINIMUM SERVICE CLEARANCE
A
C
B
400 mm
SERVICE / AIRFLOW CLEARANCE
COMP.
OUTDOOR COIL
MINIMUM SERVICE ACCESS AREAS
AND AIRFLOW CLEARANCES
HEIGHT CLEARANCE
= 1500 mm
NOTES:
1. Do not scale drawing. All dimensions are in mm
unless specified. Refer to corresponding unit
dimensional drawing for mounting hole details.
2. Service Access Areas and Spaces for Airflow Clearances given are
suggested minimum based on the condition that the spaces around the
units are free from any obstructions and a walkway passage of 1000mm
between the units or between the unit and the outside perimeter is
available.
3. Minimum service access areas and spaces for airflow clearances are
responsibilities of the installer, ActronAir will not be held liable for any
extra charges incurred due to lack of access and space for airflow.
4. Under all circumstances, condenser air must not recirculate back onto
condenser coil. Keep all clearance free of any obstructions.
5. Maximum External Static of Outdoor Fans is 5 Pa.
6. STACKING OF UNITS: Ensure that minimum airflow and clearances are met.
7. Refer to pipe Connection Details on Specifications Sheet.
8. MTG C-C DIST = Mounting Centre to Centre Distance.
9. Use M12 bolt for feet mounting.
THIRD ANGLE
PROJECTION