Installation and Commissioning Guide
Advance Outdoor Units
Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
31
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
Wiring Configuration : Recommended
NOTES
4
INDOOR UNIT
DATA CONTROL
CABLE
OUTDOOR UNIT
1
3
LM-RS-2
(OPTIONAL)
AERSS
(OPTIONAL)
LR7-1
WALL CONTROLLER
3
(OPTIONAL)
2c
2a
NEO
WALL CONTROLLER
1
(OPTIONAL)
2b
NEO
WALL CONTROLLER
2
(OPTIONAL)
Item
Description
Maximum Cable Length
1 to 4
Outdoor PCB to Indoor PCB
100 m
4 to 2a, 4 to 2b
Indoor PCB to Wall Controller
90 m
4 to 2c
Indoor PCB to Wall Controller 3
100 m
4 to 3
Indoor PCB to Remote Sensor
100 m
Description
Cable Type
Indoor to Wall Controller
Cat5e UTP (AWG 24) Data Cable
Indoor to Remote Sensor
Cat5e UTP (AWG 24) Data Cable
Indoor to Outdoor Data Cable
2 Core (1 Pair) Twisted Pair, 7/0.30 (0.5mm
2
) Shielded Data Cable