Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
Installation and Commissioning Guide
Advance Outdoor Units
42
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
Indoor Fan Commissioning
EVV140S / EFV140S
NOTES
* Only applicable to Third Party controllers
W = Indoor Fan Power, Watts
PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the LR7-1, LC7-2, NEO or Outdoor Board).
APPLICATION RANGE (COMPRESSOR ON) *
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
500
28
100
35
151
40
206
46
268
51
330
550
32
121
39
179
44
227
50
295
55
360
600
37
145
44
207
49
263
54
326
60
394
630
40
162
47
220
52
285
58
351
63
417
650
42
173
48
229
54
299
60
368
65
432
700
47
197
53
260
60
334
65
400
72
480
750
52
227
60
303
66
379
72
449
96
709
Default Fan Speed Value at 100 Pa
Speed
Default PWM (adjustable)
Indoor Fan PWM Limits
High PWM (%)
60
High PWM Limit
99
Medium PWM (%)
47
Low PWM Limit
28
Low PWM (%)
35