Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
Installation and Commissioning Guide
Advance Outdoor Units
48
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
EVV180S / EFV180S
NOTES
* Only applicable to Third Party controllers
W = Indoor Fan Power, Watts
PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the LR7-1, LC7-2, NEO or Outdoor Board).
APPLICATION RANGE (COMPRESSOR ON) *
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
680
43
184
50
250
56
317
61
385
67
452
700
45
192
52
266
58
334
63
400
70
471
750
51
228
58
304
63
372
69
446
99
535
800
57
262
63
340
69
419
80
505
850
63
305
69
386
78
484
900
69
348
77
440
91
540
950
77
404
85
498
1000
85
461
1020
89
486
Default Fan Speed Value at 100 Pa
Speed
Default PWM (adjustable)
Indoor Fan PWM Limits
High PWM (%)
99
High PWM Limit
99
Medium PWM (%)
69
Low PWM Limit
43
Low PWM (%)
50
MOTOR / BLOWER UNIT