Installation & Commissioning Guide - ESP Platinum OD Split Ducted Units
Doc. Part No. 0525-053
Ver. 5 200129
Page 8 of 36
OUTDOOR UNIT DIMENSIONS / CLEARANCES CRQ4-19AS
STANDARD PLATINUM MODEL
C
OVERALL NOMINAL DIMENSION (H x W x L)
= 1045 x 1460 x 580
USE M12 BOLT FOR FEET MOUNTING
UNIT MODEL
NUMBER
UNIT
WEIGHT
(kg)
CORNER WEIGHTS
(kg)
A
B
C
D
CRQ4-19AS
163
26.1
55.3
27.0
54.6
SIDE VIEW
FRONT VIEW
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
HEIGHT CLEARANCE
= 1500
COMP.
A
B
C
D
OUTDOOR COIL
600 mm
SERVICE
CLEARANCE
(COMPRESSOR
AND
ELECTRICALS)
400 mm
SERVICE ACCESS / AIRFLOW CLEARANCE
300 mm
SER
VICE /
AIRFLOW
CLEARANCE
NIL - TO - MINIMUM SERVICE CLEARANCE
NOTES:
1.
Do not scale drawing. All dimensions are in mm unless specified. Refer
to corresponding unit dimensional drawing for mounting hole details.
2.
Service Access Areas and Spaces for Airflow Clearances given above
are suggested minimum based on the condition that the spaces around
the units are free from any obstructions and a walkway passage of
1000mm between the units or between the unit and the outside perimeter
is available.
3.
Minimum service access areas and spaces for airflow clearances are
responsibilities of the installer, ActronAir will not be held liable for any
extra charges incurred due to lack of access and space for airflow.
4. Under all circumstances, condenser air must not recirculate back onto
condenser coil. Keep all clearance free of any obstructions.
5.
Maximum External Static of Outdoor Fans is 5 Pa.
6.
STACKING OF UNITS: Ensure that minimum airflow and clearances are
met.
7.
Refer to Pipe Connection Details on Specifications Sheet.
8. MTG C-C DIST = Mounting Centre to Centre Distance.
9.
Use M12 bolt for feet mounting.
THIRD ANGLE
PROJECTION
PLEASE NOTE THAT UNDER ALL CIRCUMSTANCES, CONDENSER
AIR MUST NOT RECIRCULATE BACK ONTO CONDENSER COIL.
KEEP ALL CLEARANCES FREE OF ANY OBSTRUCTIONS
TOP VIEW
1045
O/A
1125
(MTG C-C DIST)
1010
110 115
60
57.5
115 110
57.5
555
517
(MTG C-C DIST)
25
25
35
30
OUTDOOR
AIR INLET
OUTDOOR
AIR OUTLET
ELECT. ACCESS
2 x Ø 25.4 mm (1")
GAS PIPE
Ø 19.1 mm (3/4")
SWAGED
LIQUID PIPE
Ø 9.5 mm (3/8")
SWAGED
980
1460 O/A
355
525
580
O/A
255
COMP
DRAIN
POINT
OUTDOOR COIL
OUTDOOR
AIR INLET
OUTDOOR
AIR INLET
OUTDOOR
AIR INLET
110
340
500
Содержание CRQ2-14AS
Страница 35: ...THIS PAGE IS INTENTIONALLY LEFT BLANK ...