Above illustration shown as calculation examples only. It is the responsibility of the Installer
to design an efficient refrigeration piping lay out for optimum unit performance.
TABLE 2: REFRIGERATION PIPING
Outdoor Model
CRQ2-14AS
CRQ3-17AS
CRQ4-19AS
Indoor Model
ERQ2-14AS
ERQ3-17AS
ERQ4-19AS
Maximum Equivalent Pipe Length Range
metres
60
60
60
Maximum Vertical Height Differential
(1)
metres
20
20
20
Field Pipe Size
Liquid Line
mm (inch)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas Line
mm (inch)
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
Outdoor Pipe Size
Liquid Line
mm (inch)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas Line
mm (inch)
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
Indoor Pipe Size
Liquid Line
mm (inch)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas Line
mm (inch)
19.05 (3/4)
19.05 (3/4)
22.2 (7/8)
(2)
Note: (1) Included in maximum field pipe length.
(2) Cut Swaged End in the field to fit field pipe.
FIELD PIPE CONNECTION
EXAMPLE TOTAL EQUIVALENT FIELD PIPE LENGTH CALCULATIONS
THIRD ANGLE
PROJECTION
Drawing Release
D
E
F
C
B
A
3
2
1
5
C
D
4
6
7
8
A
B
UNIT ASSY CRV2-14AS-0200
8011-682
7/06/2015
DL
See Notes
A3
SHEET 1 OF 1
N.T.S
DRAWING NO.
MATERIAL:
DESCRIPTION:
DATE
DRAWN BY:
APPROVED BY:
SCALE:
DRAWN DATE:
DESCRIPTION
FINISH:
REV
7/06/2015
N/A
PCR
P283
F
E
REV.
A
DL
PAR
T
8011-
682
BY
A.B.N. 34 002 767 240
PH. +61 2 8814 4000
Bella Vista NSW 2153
Norwest Business Park
5 Irvine Place
written consent is prohibited
See Notes
Modifying or Distributing without
Engineering Pty Ltd. Copying,
3.
intellectual property of Actron
This drawing always remains the
ActronAir Pty Ltd
FOLD (each)
7.
3
1.
HOLE DIAMETER
0.5 / m
0.1/~0
2.
FLAT PATTERN
4.
ANGLES & SQUARENESS
0.5 / m
5.
1
GENERAL TOLERANCES
(UNLESS OTHERWISE SPECIFIED)
ALL TUBES
UNLESS OTHERWISE SPECIFIED
3rd ANGLE PROJECTION.
1.
DIMENSIONS IN MILLIMETRES.
2.
DO NOT SCALE.
3.
TUBE ENDS MUST BE ROUND AND OF FULL
4.
DIAMETER.
TUBE MUST BE CLEAN AND FREE FROM
5.
BURRS INSIDE AND OUTSIDE AND SUITABLE
OF FOR SOLDERING.
ALL BENDS 90 .
6.
ALL SHEETMETAL'S DIMENSIONS OUTISDE.
A
OUTDOOR
UNIT
V
2
INDOOR
UNIT
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Con
fi
guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. air
fl
ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci
fi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi
cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
E
1
E
2
E
3
V
1
H
1
H
2
H
3
E
4
Equivalent Pipe Length = Total Horizontal Total Vertical Length
+ Total Losses from Elbows
H = Horizontal Length
V = Vertical Length
E = Elbow Losses
Equivalent Pipe Length = (H
1
+
H
2
+
H
3
) + (V
1
+
V
2
) + (E
1
+
E
2
+
E
3
+
E
4
)