FIELD PIPE CONNECTION
The units described in this guide uses R410A refrigerant
, which operates at a pressure approximately 1.6 times
higher than a similar systems using R-22. When installing equipment using R410A refrigerant, there are number of
standards that must be met:
• •
The system of this unit operates with Polyvinylether
The system of this unit operates with Polyvinylether
(PVE) oil that rapidly absorbs moisture.
oil that rapidly absorbs moisture.
• • The maximum time any system can be opened to atmosphere is 15 minutes
The maximum time any system can be opened to atmosphere is 15 minutes.
• It is important to work with absolute cleanliness.
•
Brazing must be done with the use of Nitrogen to avoid carbon deposits into the pipes.
• The system must be evacuated thoroughly to 500 microns (see evacuation procedure).
•
The system must always be charged with R410A refrigerant in liquid state.
• •
Never allow R410a refrigerant to vent into the atmosphere. It is an offence to release refrigerant in Australia.
Never allow R410a refrigerant to vent into the atmosphere. It is an offence to release refrigerant in Australia.
• •
Always reclaim refrigerant using equipment and container dedicated for R410a system use only.
Always reclaim refrigerant using equipment and container dedicated for R410a system use only.
• •
Only qualified persons are allowed to perform any work described in this guide.
Only qualified persons are allowed to perform any work described in this guide.
• •
All work must be carried out in accordance with Australia and New Zealand refrigerant handling code of practice.
All work must be carried out in accordance with Australia and New Zealand refrigerant handling code of practice.
Maximum allowable total equivalent field pipe length is 60 metres, see diagram below. This includes all the equivalent
pipe fitting loses and vertical height difference. Vertical height difference must not exceed 20 metres. Table 1 below
shows the equivalent straight pipe length of elbow fittings.
TABLE 1: EQUIVALENT STRAIGHT PIPE LENGTH OF ELBOW FITTINGS (METRES)
Pipe size Nominal
Diameter
90
o
Long Radius
Elbow
90
o
Short Radius
Elbow
45
o
Long Radius
Elbow
45
o
Short Radius
Elbow
9.5 (3/8”)
0.24
0.36
0.09
0.14
15.9 (5/8”)
0.30
0.45
0.15
0.23
19.1 (3/4”)
0.40
0.60
0.18
0.27
22.2 (7/8”)
0.46
0.69
0.21
0.32
25.5 (1”)
0.52
0.78
0.24
0.36
28.6 (1-1/8”)
0.55
0.83
0.27
0.41
Selected field pipe sizes must match the recommended sizes in table above. If the installation requires different field
pipe diameter due to different application condition other than recommended, contact Actron Air for advice.
Most of unit pipe connections are factory swaged to easily fit to the recommended field pipe diameter.
When it is required to install other refrigeration devices, such as refrigerant drier, solenoid valve and the like, include
the equivalent straight pipe length of the device in the calculation of total equivalent field pipe length.
A = EQUIVALENT PIPE LENGTH,
60 meters (max)
B = VERTICAL HEIGHT,
20 meters (max)
CAUTION
THIRD ANGLE
PROJECTION
Drawing Release
D
E
F
C
B
A
3
2
1
5
C
D
4
6
7
8
A
B
UNIT ASSY CRV2-14AS-0200
8011-682
7/06/2015
DL
See Notes
A3
SHEET 1 OF 1
N.T.S
DRAWING NO.
MATERIAL:
DESCRIPTION:
DATE
DRAWN BY:
APPROVED BY:
SCALE:
DRAWN DATE:
DESCRIPTION
FINISH:
REV
7/06/2015
N/A
PCR
P283
F
E
REV.
A
DL
PAR
T
8011-
682
BY
A.B.N. 34 002 767 240
PH. +61 2 8814 4000
Bella Vista NSW 2153
Norwest Business Park
5 Irvine Place
written consent is prohibited
See Notes
Modifying or Distributing without
Engineering Pty Ltd. Copying,
3.
intellectual property of Actron
This drawing always remains the
ActronAir Pty Ltd
FOLD (each)
7.
3
1.
HOLE DIAMETER
0.5 / m
0.1/~0
2.
FLAT PATTERN
4.
ANGLES & SQUARENESS
0.5 / m
5.
1
GENERAL TOLERANCES
(UNLESS OTHERWISE SPECIFIED)
ALL TUBES
UNLESS OTHERWISE SPECIFIED
3rd ANGLE PROJECTION.
1.
DIMENSIONS IN MILLIMETRES.
2.
DO NOT SCALE.
3.
TUBE ENDS MUST BE ROUND AND OF FULL
4.
DIAMETER.
TUBE MUST BE CLEAN AND FREE FROM
5.
BURRS INSIDE AND OUTSIDE AND SUITABLE
OF FOR SOLDERING.
ALL BENDS 90 .
6.
ALL SHEETMETAL'S DIMENSIONS OUTISDE.
A
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Con
fi
guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. air
fl
ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci
fi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi
cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
B
OUTDOOR UNIT
INDOOR UNIT
A
FIELD PIPE
(Installer to Supply)
Содержание CRQ2-14AS
Страница 35: ...THIS PAGE IS INTENTIONALLY LEFT BLANK ...