Installation and Commissioning Guide

Split Ducted Indoor Units

Installation and Commissioning Guide - Split Ducted Indoor Unit

Doc. No.0525-074  

Ver. 3  200811

 

 

9

04.04.  EVA170S

DUCT WORK

DUCT WORK

850 MM

SERVICE

CLEARANCE

850 MM

SERVICE

CLEARANCE

(ELECTRICALS)

EC

ID FAN

EC

ID FAN

INDOOR COIL

HEIGHT CLEARANCE = 410MM

MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES

OVERALL NOMINAL DIMENSION (H X W X L)

= 412 X 1290 X 615

SUPPLY DUCT (H X W) = 300 X 715

RETURN DUCT = 340 X 1100

CONDENSATE DRAIN CONNECTION  

= 20MM OD

UNIT MODEL NUMBER

UNIT  WEIGHT

(kg)

EVA150S

56

1100

80

715

20

20

INDOOR COIL

412

O/A

615 O/A

1252

40

300

72

40

340

22

50

115

248.5

248.5

575

SUPPLY

AIR

RETURN

AIR

1290 O/A

40

535

65

47

EC

INDOOR

FAN

EC

INDOOR

FAN

SUPPLY AIR

TOP VIEW

FRONT VIEW

SIDE VIEW

NOTES: 

1.  Do not scale drawing. All dimensions are 

in mm unless specified.

2.  Service Clearances given are suggested 

minimum based on the condition that 
the spaces around the units are free 
from any obstructions and a walkway 
passage of 1000mm between the units 
or between the unit and the outside 
perimeter is available. 

3.  Minimum service access clearances are 

responsibilities of the installer, ActronAir 
will not be held liable for any extra 
charges incurred due to lack of access.  

THIRD ANGLE

PROJECTION

Содержание Classic 2 EAA130S

Страница 1: ...S EVA230S EAA130S EFA130S EAA150S EFA150S EAA170S EFA170S EAA200S EFA200S EAA230S EFA230S Above unit illustration shown is an EVA130S unit EVA100S has a single fan configuration Split fan coil has a separate coil and fan section IMPORTANT NOTE Please read this manual carefully before installing or operating your air conditioning unit That s better That s Actron ...

Страница 2: ...ece Fan Coil 12 05 01 Coil Section 12 05 02 Fan Section 16 06 Installation Instructions 19 07 Unit Lifting Procedures 21 07 01 Crane Lifting Method 21 07 02 Fork Lift Method 22 08 Safety Drain Tray 23 09 Zone Barrel Installation Instructions 24 10 Electrical Installation 25 11 Wiring Diagram 26 12 Split Unit Electrical Connection 27 13 Maximum Cable Lengths 29 13 01 Wall Controller Options 29 13 0...

Страница 3: ... unit components and accessories for any sign of damage If there is any damage to the unit contact ActronAir Customer Care Department immediately on 1300 522 722 to obtain a Goods Return Number Check the unit nameplate to verify the model serial number electrical rated specifications are correct 01 03 Codes Regulations And Standards The installer and or contractor assumes responsibility to ensure ...

Страница 4: ...or use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely Young children should be supervised to ensure that they do not play with the appliance Installer must incorporate a means of electrical disconnection isolator in the sub mains fixed wiring in accordance with AS NZS 3000 2018 also known as A...

Страница 5: ... Indoor Unit Doc No 0525 074 Ver 3 200811 5 03 Components Overview 03 01 Indoor Unit Components Overview EC MOTOR INDOOR UNIT ID FAN Single Fan for EVA100S ELECTRICAL BOX COVER ID COIL INDOOR CONTROL PANEL 03 02 Indoor Unit Electrical Panel Overview INDOOR UNIT CONTROL BOARD EMC FILTER for some models TRANSFORMER ...

Страница 6: ... OD FRONT VIEW SIDE VIEW HEIGHT CLEARANCE 340MM DUCT WORK DUCT WORK 850 MM SERVICE CLEARANCE 850 MM SERVICE CLEARANCE ELECTRICALS 770 660 575 RETURN AIR 65 45 20 20 235 267 5 267 5 850 O A 42 595 O A 535 40 20 INDOOR FAN INDOOR COIL SUPPLY AIR 135 GAS PIPE 15 9 mm 5 8 SWAGED LIQUID PIPE 9 5 mm 3 8 SWAGED EC ID FAN INDOOR COIL MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES NOTES 1 Do not scale...

Страница 7: ...available 3 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION DUCT WORK DUCT WORK 850 MM SERVICE CLEARANCE 850 MM SERVICE CLEARANCE ELECTRICALS EC ID FAN EC ID FAN INDOOR COIL HEIGHT CLEARANCE 340MM MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES 900 715 INDOOR CO...

Страница 8: ...IGHT kg EVA150S 53 1100 80 715 20 20 INDOOR COIL 412 O A 615 O A 1252 40 300 72 40 340 22 50 115 248 5 248 5 575 SUPPLY AIR RETURN AIR 1290 O A 40 535 65 47 EC INDOOR FAN EC INDOOR FAN SUPPLY AIR TOP VIEW FRONT VIEW SIDE VIEW NOTES 1 Do not scale drawing All dimensions are in mm unless specified 2 Service Clearances given are suggested minimum based on the condition that the spaces around the unit...

Страница 9: ...IGHT kg EVA150S 56 1100 80 715 20 20 INDOOR COIL 412 O A 615 O A 1252 40 300 72 40 340 22 50 115 248 5 248 5 575 SUPPLY AIR RETURN AIR 1290 O A 40 535 65 47 EC INDOOR FAN EC INDOOR FAN SUPPLY AIR TOP VIEW FRONT VIEW SIDE VIEW NOTES 1 Do not scale drawing All dimensions are in mm unless specified 2 Service Clearances given are suggested minimum based on the condition that the spaces around the unit...

Страница 10: ...are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION DUCT WORK DUCT WORK 850 MM SERVICE CLEARANCE 850 MM SERVICE CLEARANCE ELECTRICALS EC ID FAN EC ID FAN INDOOR COIL HEIGHT CLEARANCE 410MM MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES OVERALL NOMINAL DIMENSION H X W X L 435 X 1420 X 680 SUPPLY DUC...

Страница 11: ...SWAGED SAFETY DRAIN Ø 25mm ID PRIMARY DRAIN Ø 25mm ID TOP VIEW FRONT VIEW SIDE VIEW NOTES 1 Do not scale drawing All dimensions are in mm unless specified 2 Service Clearances given are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000mm between the units or between the unit and the outside perimeter is available ...

Страница 12: ...054 X 342 SUPPLY DUCT H X W 345 X 900 RETURN DUCT 345 X 900 UNIT MODEL NUMBER UNIT WEIGHT kg EAA130S 24 DUCT WORK TO FAN SECTION 0M MIN 6M MAX 850 MM SERVICE CLEARANCE TOP VIEW COIL SECTION DUCT WORK HEIGHT CLEARANCE 340MM MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES 850 MM SERVICE CLEARANCE NOTES 1 Do not scale drawing All dimensions are in mm unless specified 2 Service Clearances given ar...

Страница 13: ...extra charges incurred due to lack of access THIRD ANGLE PROJECTION DUCT WORK TO FAN SECTION 0M MIN 6M MAX 850 MM SERVICE CLEARANCE TOP VIEW COIL SECTION DUCT WORK HEIGHT CLEARANCE 340mm MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES 850 MM SERVICE CLEARANCE 20 1212 20 176 900 176 51 345 410 O A 131 156 43 25 31 1190 MTG C C DIST 31 342 O A 302 94 29 15 23 81 22 199 283 131 81 22 283 345 51 1...

Страница 14: ...or any extra charges incurred due to lack of access THIRD ANGLE PROJECTION DUCT WORK TO FAN SECTION 0M MIN 6M MAX 850 MM SERVICE CLEARANCE TOP VIEW COIL SECTION DUCT WORK HEIGHT CLEARANCE 410mm MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES 850 MM SERVICE CLEARANCE 21 1318 21 362 61 435 O A 133 1094 133 158 143 10 25 33 1294 MTG C C DIST 33 342 O A 302 15 39 153 28 76 87 237 310 87 130 310 22...

Страница 15: ...ssage of 1000mm between the units or between the unit and the outside perimeter is available 3 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION 21 1368 21 410 61 486 O A 158 1094 165 160 11 11 342 O A 13 28 302 360 87 22 131 69 89 238 360 22 18 30 39 153 410 61 158 1...

Страница 16: ...harges incurred due to lack of access THIRD ANGLE PROJECTION MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES 850 MM SERVICE CLEARANCE TOP VIEW FAN SECTION DUCT WORK DUCT WORK FROM COIL SECTION 0M MIN 6M MAX 850 MM SERVICE CLEARANCE HEIGHT CLEARANCE 340mm 189 168 51 408 O A 152 240 228 240 152 1012 1072 O A 43 322 43 11 990 MTG C C DIST 11 87 270 5 11 990 MTG C C DIST 11 282 362 O A 282 56 900 ...

Страница 17: ...ARANCE TOP VIEW FAN SECTION DUCT WORK DUCT WORK FROM COIL SECTION 0M MIN 6M MAX 850 MM SERVICE CLEARANCE HEIGHT CLEARANCE 410mm NOTES 1 Do not scale drawing All dimensions are in mm unless specified 2 Service Clearances given are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000mm between the units or between the ...

Страница 18: ...around the units are free from any obstructions and a walkway passage of 1000mm between the units or between the unit and the outside perimeter is available 3 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION 1207 236 337 61 337 236 61 305 117 483 O A 91 322 70 1269 O...

Страница 19: ...order to minimize the transfer of noise and vibration into building structures An optional hanging bracket assembly and rubber grommet supplied as standard with EVA230S is also available to secure the indoor unit into the roof rafters This installation configuration is most suitable for installation that require the unit to be rigidly secured up from the roof joist Condensate and Safety Tray Drain...

Страница 20: ... fan coil by both of the supply air plenum and the twin spigot duct plate Fan Coil With Vertical Discharge Optional An upright Fan Coil with vertical supply air discharge is also available wherein installation applications require the placement of the unit down in a closet basement or garage Please refer to the Technical Catalogue of your indoor unit for dimensions installation details and specifi...

Страница 21: ...ing procedure and unit model shown are suggestions and for illustration purposes only It is highly recommended that installer observe current industry safe rigging and lifting procedure DETAIL A PALLET INDOOR UNIT Slip nylon slings through the pallet Connect the loop ends of slings into shackle FIGURE 1 A Provide rubber pads to prevent damage to the unit Equipment Required For Crane Lifting 1 x Sh...

Страница 22: ...to electrical panel and pipes x x Procedure 1 To move the unit around with a forklift insert the fork tines through the unit feet assembly as shown in Fig 2 2 Do not lift the unit through the electrical panel end of the unit See illustration for location of electrical panel end CAUTION Length of fork lift tines must pass the unit middle section in order to safely carry the unit Pallet fork lifting...

Страница 23: ...ONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION INSTALL A T PIECE AS AN AIR VENT FOR LONG DRAIN RUNS CLEAR PLASTIC INSPECTION TUBE P V C ELBOW CLAMP BANDS SEAL WITH SILICONE SEALANT PREFERRED METHOD OF CONNECTING P TRAP P V C ELBOW 25MM 15MM P TRAP ENSURE DRAIN PIP...

Страница 24: ...S YOU WILL REQUIRE THE APPLICABLE ZONE KIT INCLUSIONS INSTALLATION INSTRUCTIONS AS PER DETAILED LIST OPTIONAL EXTRAS SPARE PARTS INTEGRATED ZONE BARRELS OPERATE WITH M SERIES CONTROLS ONLY 24 VOLT 8 ZONE KIT 8Z 24V AMZ 24V ZONE CARD 20VA 240 TO 24 VOLT TRANSFORMER INSTALLATION INSTRUCTIONS MOUNTING SCREWS LENGTH OF ALL BARRELS MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY...

Страница 25: ...cement under warranty Wiring Diagram The wiring diagrams specific for your air conditioning system are located on the inside panel of the control panel lid Always refer all wiring installation servicing and troubleshooting of this equipment to this diagram to ensure correct electrical connections are satisfied Supply Power Requirements and Procedures It is the installer s responsibility to provide...

Страница 26: ... B S3 G COM A A B B G G COIL TEMP INDOOR FAN 24VAC TX PWM INDOOR FAN OUTDOOR 485 AUX 485 WALL CONTROLLER TEMP SENSORS AUX OUT AUX IN ICB WALL CONTROLLER MAINS SMPS 240VAC 12VDC AC L AC N V V A N ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 12V A B G FIELD WIRING BY INSTALLER FIELD WIRING BY INSTALLER CABLE MUST BE 2 CORE 7 0 30 SHIELDED TWISTED PAIR DATA CABLE WITH SCREEN WIRE CONNECTED...

Страница 27: ...e back of electrical box cover MAINS WIRING 230 400VAC Single Phase Neutral Earth 50Hz Three Phase Neutral Earth 50Hz INTER CONNECTING POWER CABLE 230VAC Single Phase Neutral Earth 50Hz DATA CABLE TO WALL CONTROL Cat5E UTP AWG 24 Data Cable EXTRA LOW VOLTAGE DATA CONTROL WIRING 2 Core Shielded Twisted Pair 7 0 30 0 5mm2 Data Cable 2 1 4 3 SUB MAIN TO UNIT INDOOR UNIT WALL CONTROL SUB MAINS ISOLATO...

Страница 28: ... Terminal in Outdoor Unit match the Data Terminal in Indoor unit Outdoor Unit Data Terminal Green Plug Terminal A White Wire Terminal B Black Wire Terminal G Shield Wire Indoor Unit Data Terminal Green Plug Terminal A White Wire Terminal B Black Wire Terminal G Shield Wire Insert data cable through the lower snap bushing and first cable tie on the right hand side of the electrical panel Connect co...

Страница 29: ... 20 0 2 5 1 0 CRA230T EVA230S EFA230S CCA230T EVA230S EFA230S 25 0 4 0 1 0 Suggested Minimum Cable Size should be used as a guide only refer to AS NZS 3000 Australian New Zealand Wiring Rules for more details 13 Maximum Cable Lengths 13 01 Wall Controller Options Maximum of three 3 wall controllers in below combinations is allowed on unit See below table Combinations Wall Controllers WC 1 WC 2 WC ...

Страница 30: ...ALL CONTROLLER 2 OPTIONAL NOTES Diagram shown above is a general representation only Refer to individual unit wiring diagram for complete wiring connection details Long runs beside Mains cables or TV antenna cables should be avoided where possible Wiring configuration for LR7 1 and LC7 2 wall controller is the same Item Description Maximum Cable Length 1 to 4 Outdoor PCB to Indoor PCB 100 m 4 to 2...

Страница 31: ...own above is a general representation only Refer to individual unit wiring diagram for complete wiring connection details Long runs beside Mains cables or TV antenna cables should be avoided where possible Wiring configuration for LR7 1 and LC7 2 wall controller is the same Item Description Maximum Cable Length 1 to 4 Outdoor PCB to Indoor PCB 100 m 4 to 2a Indoor PCB to Wall Control 1 100 m 4 to ...

Страница 32: ...e the design of it s products therefore specifications are subject to change without notice ZB 080129 INTEGRATED ZONE BARRELS 12 300 mm 10 250 mm 16 400 mm 14 350 mm 14 350 mm 16 400 mm ZB 14 350 ZB 16 400 ITEM PART NUMBER 24 VOLT 4 ZONE KIT 4Z 24V INCLUSIONS 5 YEAR RESIDENTIAL 2 YEAR COMMERCIAL PARTS ONLY WARRANTY ROBUST METAL BARREL CONSTRUCTION 10 mm FIRE RATED POLYETHELYNE INSULATION 7 m CABLE...

Страница 33: ...H OR WH INDOOR CONTROL BOARD WALL CONTROL WIRING POWER BROWN ORANGE 485 A BLUE 485 B BLUE WHITE GND BROWN WHITE ORANGE WHITE NOT USED GREEN GREEN WHITE 15 02 NEO Wall Control Wiring Connections 15 02 01 NEO Hard Wiring WALL CONTROL WALL CONTROLLER 12V A B G CUT OFF GR GR WH INDOOR CONTROL BOARD 12V A B G RJ45 WALL CONTROL WIRING POWER BROWN ORANGE 485 A BLUE 485 B BLUE WHITE GND BROWN WHITE ORANGE...

Страница 34: ...IR 2 PAIR 2 PAIR 1 PAIR 1 PAIR 1 PAIR 2 PAIR 2 REMOTE SENSOR WIRING PAIR 1 BLUE BLUE WHITE PAIR 2 ORANGE ORANGE WHITE PAIR 3 GREEN GREEN WHITE PAIR 4 BROWN BROWN WHITE 15 04 AERSS Optional Duct Sensor Wiring Connections REMOTE SENSOR WIRING PAIR 1 BLUE BLUE WHITE PAIR 2 ORANGE ORANGE WHITE PAIR 3 GREEN GREEN WHITE PAIR 4 BROWN BROWN WHITE INDOOR CONTROL BOARD S1 S2 S3 COM TEMP SENSORS PAIR 1 PAIR ...

Страница 35: ...l controller zone lights are OFF Case 2 Multi zone system Only zones motors no common zones Only detected zones should appear to be ON in Wall Controller Menu 14 Last Zone Protection will be enabled for zone 1 only unless changed from the Wall Controller Only detected zones are toggleable Case 3 Multi zone system Common zones and zone barrel Plug zone motors into InZone Board skipping the number o...

Страница 36: ...r damage rust and dust accumulation For highly corrosive environment wash panels quarterly with water and neutral detergent solution Wax panels Repair re paint where required Insulation Visual check for insulation conditions Repair replace insulation material Fan Visual check for run out of balance and dust attached Clean off dust as necessary to negate possibility of fan running out of balance Mo...

Страница 37: ... EVA100S EVA130S EVA150S EVA170S EVA200S EVA230S 1 EC ID Fan 2520 328 1 2520 338 1 1 1 2520 334 1 2520 313 1 2 Coil Piston 4540 067 1 4540 074 1 4540 084 1 4540 088 1 4540 099 1 1 3 ID Control Board 2020 169 1 1 1 1 1 1 4 Filter Board 4080 013 1 1 5 Indoor Coil 1040 225 1 1040 169 1 1040 156 1 1040 159 1 1040 177 1 1040 154 1 7 Wall Control Cable 4070 033 1 1 1 1 1 1 8 Transformer 2045 046 1 1 1 1...

Страница 38: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...

Страница 39: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...

Страница 40: ...ed Trade Marks of Actron Engineering Pty Limited ActronAir is constantly seeking ways to improve the design of its products therefore specifications are subject to change without notice Document 0525 074 Ver 3 Issue Date 08 2020 Refrigerant Trading Authorisation No AU06394 ...

Отзывы: