Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-074
Ver. 3 200811
Installation and Commissioning Guide
Split Ducted Indoor Units
10
04.05. EVA200S
NOTES:
1. Do not scale drawing. All dimensions are
in mm unless specified.
2. Service Clearances given are suggested
minimum based on the condition that
the spaces around the units are free
from any obstructions and a walkway
passage of 1000mm between the units
or between the unit and the outside
perimeter is available.
3. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra
charges incurred due to lack of access.
THIRD ANGLE
PROJECTION
DUCT WORK
DUCT WORK
850 MM
SERVICE
CLEARANCE
850 MM
SERVICE
CLEARANCE
(ELECTRICALS)
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 410MM
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
OVERALL NOMINAL DIMENSION (H X W X L)
= 435 X 1420 X 680
SUPPLY DUCT (H X W) = 300 X 715
RETURN DUCT = 360 X 1140
CONDENSATE DRAIN CONNECTION
= 20MM OD
UNIT MODEL NUMBER
UNIT WEIGHT
(kg)
EVA200S
72
SUPPLY
AIR
715
310
310
1420 O/A
1140
78
117
630
20
20
435
O/A
INDOOR COIL
1375
90
130
SUPPLY AIR
590
40
50
680 O/A
360
50
25
110
300
25
RETURN
AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
TOP VIEW
FRONT VIEW
SIDE VIEW