5. Setting up the device
13
Menu level
Parameterisation level
Setting up the physical unit,
UnIt:
Default:
no
One can choose between the above shown physical units. It will be displayed on the 5th digit of
the display.
Number of additional setpoints,
SPCt:
Default:
00
30 additional setpoints can be defined to the initial value and final value, so linear sensor
values are not linearised. Only activated setpoint parameters are displayed.
Display values for setpoints,
dIS.01 … dIS.30:
Under this parameter setpoints are defined according to their value. At the sensor calibration,
like at final value / offset, one is asked at the end if a calibration shall be activated.
Analog values for setpoints,
InP.01 … InP.30:
The setpoints are always set according to the selected input signal. The desired analog values
can be freely parameterised in ascending order.
Device undercut,
dI.Und:
Default:
-i9999
With this function the device undercut (
_ _ _ _ _
) can be defined on a definite value. Exception is
input type
4-20 mA
, it already shows undercut at a signal <1 mA, so a sensor failure is marked.