5. Setting up the device
11
5.4. Extended parameterisation
(Professional operation level)
Menu group level
Menu level
5.4.1. Signal input parameters
Menu level
Parameterisation level
Selection of the input signal,
TYPE:
Default:
sens.u
There are several measuring input options: 0-20 mA, 4-20 mA or 0-10 VDC signals as works
calibration (without application of the sensor signal) and
SenSU
(voltage)
or
SENSA
(current) as
sensor calibration (with the sensor applied). Confirm the selection with
[P]
and the display
switches back to menu level.
Setting the end value of the measuring range,
END
:
Default:
10000
Set the end value from the smallest to the highest digit with
[
▲
] [
▼
]
and confirm each digit with
[P]
. A minus sign can only be parameterized on the highest value digit. After the last digit, the
display switches back to the menu level. If
Sens
was selected as input option, you can only
select between
noca
and
cal.
With
noca
, only the previously set display value is taken over, and
with
cal
, the device takes over both the display value and the analogue input value.
Setting up the start/offset value of the measuring range,
offs
:
Default:
0
Enter the start/offset value from the smallest to the highest digit with
[
▲
] [
▼
]
and confirm each
digit with
[P]
. After the last digit the display switches back to the menu level. If
Sens
was
selected as input option, you can only select between
noca
and
cal.
With
noca
, only the
previously set display value is taken over, and with
cal
, the device takes over both the display
value and the analogue input value.