ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
14
12
5. Setting up the device
Menu level
Parameterisation level
Setting the decimal point,
dot
:
Default:
0
The decimal point on the display can be moved with
[
▲
] [
▼
]
and confirmed with
[P]
. The
display then switches back to the menu level again.
Setting up the display time,
SEC
:
Default:
1.0
The display time is set with
[
▲
] [
▼
]
. The display moves up in increments of 0.1 up to 1 second
and in increments of 1.0 up to 10.0 seconds. Confirm the selection by pressing the
[P]
button.
The display then switches back to the menu level again.
Rescaling the measuring input values,
EndA:
Default:
10000
With this function, you can rescale the input value of
e.g. 19.5 mA
(works setting) without
applying a measuring signal. If sensor calibration has been selected, these parameters are not
available.
Rescaling the measuring input values,
OFFA:
Default:
0
With this function, you can rescale the input value of
e.g. 3.5 mA
(works setting) without
applying a measuring signal. If sensor calibration has been selected, these parameters are not
available.
Setting up the tare/offset value,
tArA:
Default:
0
The given value is added to the linearized value. In this way, the characteristic line can be
shifted by the selected amount.
Setting up the balance point,
Adj.pt:
Default:
08000
The balance point for the final value can be chosen from the measuring range by
Sens.u
with
0…10V or
Sens.A
with 0…20mA in %. The preset 80.000% result from the widespread detuning
of the melt pressure sensors.
then