6.3.3 Isolation
Logic and field connections are isolated (see OUTPUT specifications).
Individual ports are also isolated from each other. However, output lines of
individual ports share a common connection and are not isolated from each
other. Separate port commons are provided to facilitate port-to-port
working voltage isolation of 100VAC or DC. Logic and field lines are isolated
from each other for working voltages up to 250VAC or DC on a continuous
basis (unit will withstand a 1450V AC dielectric strength test for one minute
without breakdown).
6.3.4 Vibration and Shock Standards
The AcroPack passes the following Vibration and Shock standards.
Vibration, Sinusoidal Operating: Complies with IEC 60068-2-6: 10-500Hz,
5G, 2 Hours/axis
Vibration, Random Operating: Complies with IEC 60068-2-64: 10-500Hz,
5G-rms, 2 Hours/axis
Shock, Operating: Complies with IEC 60068-2-27: 30G, 11ms half sine,
50G, 3mS half sine, 18 shocks at 6 orientations for both test levels
6.3.5 EMC Directives
The AcroPack complies with EMC Directive 2004/108/EC.
Immunity per EN 61000-6-2:
Electrostatic Discharge Immunity (ESD), per IEC 61000-4-2.
Radiated Field Immunity (RFI), per IEC 61000-4-3.
Electrical Fast Transient Immunity (EFT), per IEC 61000-4-4.
Surge Immunity, per IEC 61000-4-5.
Conducted RF Immunity (CRFI), per IEC 61000-4-6.
Emissions per EN 61000-6-4:
Enclosure Port, per CISPR 16.
Low Voltage AC Mains Port, per CISPR 16.
Note: This is a Class A product