89
There are 120 communication addresses for user customization. Address 5000-5119 and
5300-5419, the corresponding data values can be customized. If the value of 5300 is written as
2010, the address 5000 is the same as the address 2010 data.
Example:
Suppose
the
user
needs
to
read
and
write
the
original
address
2003,2300,2307,2309,2335,2357,2758,2800 frequently. These addresses are not continuous
addresses, each read an address data, need to send a MODBUS read command.
In this case, the efficiency can be improved by customizing the address function: the user can
write the address 5300-5307 as 2003,2300,2307,2309,2335,2357,2758,2800 respectively, so that
the definition of the address 5000-5007, read and write, value range and so on will correspond to
the above address one by one. At this time, the user only needs to send a read command to achieve
all data read and write.
11
11
11
11 Examples
Examples
Examples
Examples of
of
of
of ordering
ordering
ordering
ordering
Example: specific model: ARD2F-100/QJMCSU-90L
Technical requirements: motor power 37 KW, 4-20 mA analog output ,alarm output, voltage
loss restart
Communication protocol : RS485 protocol, MODBUS RTU protocol
Auxiliary power: AC 220V
Display mode :90L
Note: main body and transformer connection length 1 m; main body and display unit
connection length 1.5 m.