40
Alarm
on/off
Off
Tripping
on/off
Off
Temperature
protection
PTC type
on/off
On
Return
resistanse value
0
(
Shut down
)、
100-30000
0
Ω
Alarm
resistance value
100~30000
1600
Ω
Tripping
resistance value
100~30000
3600
Ω
Tripping delay
0.1~600
5.0
S
Alarm
on/off
On
Tripping
on/off
On
External fault
Tripping delay
0.1~600
5.0
S
Alarm
on/off
Off
Tripping
on/off
Off
Protect
the
parameter
s (high
speed)
Refer to the low speed protection setting sheet
7
Control
parameter
s
Control access
Control access
Display unit, in -
place,
communication,
remote, three choice
one, two choice one,
full control
All control
Start method
Start mode
Protection mode,
manual mode,
two-step mode,
two-speed mode,
star triangle,
auto-step-down
Protected
mode
start1delay
0.1-600
3.0
S
Self start
Self start mode
recover/start
start
Self start delay
0.1~600
5.0
S
Self start
control
on/off
Off
Voltage loss
restart
Recovery
voltage
70-95%
80
%
Voltage drop
50-90%
50
%
Sway electric
time
0.5-300.0
5.0
S