start control set to manual mode, local control), DO1 relay disconnected,KM coil
power loss, motor stop work.
9.3 ARD2F Electrical motor protector forward/reverse wiring diagram
Forward and reverse starting: motor starting and stopping are controlled by protector,
Press the Start 1 button on the display unit, Display unit control), DO1 relay (default
start 1 function) closed, Close the KM1's main contacts, Motor starting; Press the
"start 2" button on the display unit, DO1 relay (default start 1 function) disconnected,
DO2 relay (default start 2 function) closed,close the KM2's main contacts, Motor
reverse start. Press the stop button on the panel, DO2 relay disconnected 3s, with stop
function in pulse output mode KM1
、
KM2 coil is out of power, The motor stopped
working.
Click switch input DI2( default start 1 function, Start control set to manual mode,
Local control), DO1 relay (default start 1 function) closed, Close the KM1's main
contacts, Motor starting; Click switch input DI3( default start 2 function), DO1 relay
(default start 1 function) disconnected, DO2 relay (default start 2 function) closed,
close the KM2's main contacts, Motor reverse start. Click switch input DI1( default
stop function), DO2 relay disconnected, KM1
、
KM2 coil is out of power, The motor
stopped working.