38
allowed/forbidden
under-power
Alarm
delay
0.1-600.0s
0.1s
s
Tripping delay
0.1-600.0s
5.0s
s
Alarm threshold
0-100%
80%
%
Trip Threshold
0-100%
50%
%
Action stage
Start:
allowed/forbidden
Allow
Run:
allowed/forbidden
Allow
Stop:
allowed/forbidden
Forbidden
Return
coefficient
5%
Alarm, trip
allowed
Alarm:allowed/forbid
den
Forbidden
Trip:
allowed/forbidden
Forbidden
temperature pr
otection
NTC/PTC
NTC/PTC
PTC
Alarm delay
0.1-600.0s
0.1s
s
Tripping delay
0.1-600.0s
5.0s
s
Alarm threshold
100-30000
Ω
1600
Ω
Ω
Trip Threshold
100-30000
Ω
3600
Ω
Ω
Action stage
Start:
allowed/forbidden
Allow
Run:
allowed/forbidden
Allow
Stop:
allowed/forbidden
Forbidden
Reset method
Manual and automatic
automatic
Return
resistanse value
100-30000
Ω
1500
Ω
Alarm, trip
allowed
Alarm:allowed/forbid
den
Forbidden
Trip:
allowed/forbidden
Forbidden
external fault
Alarm delay
0.1-600.0s
0.1s
s
Tripping delay
0.1-600.0s
5.0s
s
Action stage
Start:
allowed/forbidden
Allow
Run:
allowed/forbidden
Allow
Stop:
Forbidden