68
Bit6 blocking alarm;
Bit7 blocking alarm;
Bit8 current imbalance
alarm;
Bit9 PTC temperature
alarm;
Bit10 external fault alarm;
Bit11 start timeout alarm;
Bit12 power alarm;
Bit13 underpower alarm;
Bit14 phase sequence
alarm;
Bit15 short circuit alarm.
(0- No alarm, 1- Alarm)
653
0963
Alarm
allowed/forbidden 2
R/W
Bit0
fixed
time
limit
overload alarm;
Bit1
voltage
imbalance
alarm;
Bit2
overflow
protection
alarm;
Bit3 starting times alarm;
Bit4 running time alarm;
Bit5 fault times alarm
word
654
0964
Trip level
R/W
1
、
2
、
3
、
5
、
10
、
15
、
20
、
25
、
30
、
35
、
40
word
655
0965
tE Trip level
R/W
2
、
3
、
4
、
5
、
6
、
8
、
10
、
12
、
15
word
656
0966
Start setting
R/W
100-800%
word
657
0967
Reset method
R/W
0-Off
;
1-On
word
658
0968
Overload cooling time
R/W
0-30min
word
659
0969
Overload
alarm
threshold
R/W
1-99%
word
660
096B
Overload starting
protection screen time
R/W
0-25.0
word
661
096C
Ground fault alarm
threshold
R/W
20%-100%
662
096D
Ground fault trip
threshold
R/W
20%-100%
663
096F
Ground fault protection
delay
R/W
0.1
~
600.0s
word
664
0970
Trip mode
R/W
Bit
(
0- circuit breaker 1-
contactor
)
word
665
0971
Ground fault starting
R/W
0-25.0
word