47
scaling factor is the actual
value
2
0x02
L3 Phase current (full
wave/fundamental
wave)
R
word
R
word
3
0x03
leakage current
R
0-3000mA
word
Ground current percent
R
0-100%
4
0x04
Uab Line voltage (full
wave/fundamental
wave)
R
0~1999.9
word
5
0x05
Ubc Line voltage (full
wave/fundamental
wave)
R
0~1999.9
word
6
0x06
Uca Line voltage (full
wave/fundamental
wave)
R
0~1999.9
word
7
0x07
Apparent
power
(full
wave/fundamental
wave)
R
32 bit signed number,
High characters before, low
characters after
The fundamental value is
when
the
fundamental
switch is turned on
高字
8
0x08
R
低字
9
0x09
Active power (full
wave/fundamental
wave)
R
高字
10
0x0A
R
低字
11
0x0B
Active electric energy
(full wave/fundamental
wave)
R
32 bit unsigned number,
High characters before, low
characters after
The fundamental value is
when
the
fundamental
switch is turned on
高字
12
0x0C
R
低字
13
0x0D
Power
factor
(full
wave/fundamental
wave)
R
-1.000-1.000 Unit 0.001
word
14
0x0E
Current
imbalance Degree
R
0-100%
word
15
0x0F
Cumulative
heat
capacity Percentage
R
0-100%
word
16
0x10
Temperature value
R
0-65535
Ω
word
17
0x11
motor this run time
R
0-65535 hour
word
18
0x12
motor this stop time
R
0-65535 hour
word
19
0x13
Switching input/output
R/W
Bit0-bit9 corresponds to
switch volume input
Di1-DI10, Bit10
corresponds to DO6, and
BIT11-15 corresponds to
DO1-DO5
word