29
KOOLMASTER PP20-VS2 rev.00
KOOLMASTER PP20-VS2
Temperature Compensation —
The temperature
compensation is expressed as a percentage
per degree difference between the ambient
temperature and the average reading of the in-
let’s probes. For each degree above or below
the average temperature, the inlet will open or
close using the compensation value.
Operating mode —
Select
“Auto”
to let the
controller to control the opening of the chosen
air inlet; select ”Manual” to change the inlet
position manually (the controller does not
set off any opening alarm when an inlet is
controlled manually).
Manual mode —
This menu appears when the
air inlet is in manual mode. Select
“Open”
or
“Close”
to move the actuator or select
“Off”
to stop it.
If the inlet is controlled by a timer, please
make a manual reset of the actuator’s
position after each manual opening of
the air inlet (see section 6.5.3).
Test mode —
This is the room temperature
that is used in test mode. This value can only
be modified in the
“Test Mode”
menu (see
section 4.12).
Min Fan Speed —
During the minimum ventila-
tion cycles and in stage 1, the inlet will use its
minimum ventilation position as long as the
fan speed is lower than the
“Min Fan Speed”
and will start opening further if the fan speed
gets higher than this. Set the minimum fan
speed to the desired value.
Closed —
This is the position of the air inlet
during the
“Off Time”
portion of minimum
ventilation cycles. Set this position to the
desired value.
Min Vent —
This is the position of the air inlet
during the
“On Time”
portion of a minimum
ventilation cycle.
Stage #x —
Assign an inlet opening (in %)
with the startup of each fan stage.
Stage #x max —
Assign the inlet opening that
is reached when the variable-speed fan stage
reaches its maximum intensity.
• Over-Opening Settings
Opening
— Assign an inlet position to
the over-opening stage.
Bandwidth
— Set the temperature range
over which the inlet gradually opens from
the position associated with the last fan
stage towards the over-opening position
(see previous graph).
Total opening time —
Enter the exact time that
is required to reach the actuator’s maximum
limit switch. The controller will limit the open-
ing of the inlet according to this parameter
value. *
This parameter is accessible if the air inlet
uses a timer. It is also common to all programs.
Under Run Open Time (Advanced parameter
for timer-based inlets only) —
When a timer
ends, it may take a few seconds for the actua-
tor to actually stop moving. For this reason,
the controller can switch off the actuator’s
motor slightly before its time for the actua-
tor to reach its exact moving time without
exceeding it. This parameter ranges from
0 to 3 seconds.*
This parameter is only accessible
with the factory password and it is only shown if the
selected inlet uses a timer.
6.5.3. Actuator Reset
[For timer-based inlets only]
No reset can be made when the outside
temperature falls to a user-defined value.
This applies to automatic & manual
resets.
Resetting the actuator’s position is used to
clear accumulated time offsets caused by
the frequent openings and closings of the
inlet. The controller resets the actuator’s
position at regular intervals to make sure the
inlet position is always accurate. This reset
is performed automatically according to one
of these two methods:
Reset the minimum position only
1.
(Close mode)
Each time a reset is performed, the inlet to-
tally closes. Once the actuator’s position is
reset, the inlet returns to its previous position.
The
“Close”
pilot light of the inlet flashes while
the controller closes the inlet.
Reset toward the nearest position
2.
(Open/Close mode)
If the current inlet position is higher than 50%
at the reset time, the controller fully opens
the inlet to reset the actuator’s position; if
the current inlet position is lower than 50%,
the controller closes the inlet to perform the
reset. This way, the inlet never closes when
the room temperature already asks for a wide
opening. The
“Open”
or
“Close”
pilot light of
the inlet flashes while the controller moves
the inlet.
Make sure limit switches are located at
both ends of the actuators when using
this resetting method.
Inlet 1 Settings
Inlet 2
Auto Reset
Calib
Use to navigate
Position
0 %
Hysteresis +/-
3 %
Temp Compensation
0 %/°
Mode
Manual
Manual Mode Open/Off/Close
Test Mode
72.3 °F
Min Fan Speed
45 %
Openings
Closed
0 %
Min. Vent.
5 %
Stage 1
10 %
Stage 1 Max
15 %
Stage 2
20 %
Stage 3
30 %
Stage 4
40 %
Stage 5
50 %
Stage 6
60 %
Stage 7
70 %
Stage 8
80 %
Over Opening settings
Opening
100 %
Bandwidth
5.0 °F
Total Opening Time
2:00 m:s
Under Run Open Time
2 sec
Содержание Koolmaster PP20-VS2
Страница 47: ......
Страница 48: ...REV 00 M 890 00527 rev 00 ...