ACME Koolmaster PP20-VS2 Скачать руководство пользователя страница 39

39

KOOLMASTER PP20-VS2   rev.00

KOOLMASTER PP20-VS2

12. 

ALARMS

When an alarm occurs, the controller lights 
up the alarm pilot light, displays letters 

“AL”

 

on the LED display, and post the alarm con-
dition into the alarm log menu. Some user-
defined  alarm  conditions  may  also  activate 
the alarm relay. 

The table on the right gives a list of all pos-
sible alarm conditions. Refer to section 12.3 
to specify which of these alarm conditions 
must activate the alarm relay.

DISPLAY

MEANING

Low Temp 

Alarm

Low temperature alarm

High Temp 

Alarm

High temperature alarm

Low Pressure 

Alarm

Low static pressure alarm

High Pressure 

Alarm

High static pressure alarm

Probe #1-8 

Defect

A temperature probe is 

defective

Outside Probe 

#x Defect

Outside probe #x is 

defective

Whisker 

Switch Defect

The Whisker switch is 

defective

Water Spill 

Water consumption too 

high

Lo/Hi Water 

Usage

The water consumption 

of the last 24h is too low 

or to high compared to 

the water consumption of 

the 24h that precede.

SP Probe 

Defect

The static pressure sen-

sor is defective

Inside RH 

Probe Defect 

The indoor humidity 

probe is defective

Outside RH 

Probe Defect 

The outdoor humidity 

probe is defective

Relay panel 

comm. Error

Communication is disrupt-

ed between  the control-

ler and the relay panel.

Inlet potenti-

ometer defect

The potentiometer is 

defective.

Feeder 1-2 

run time ex-

ceeded

A feeder has been run-

ning continuously on a 

too long period of time.

Missing zero 

crossing

Problem with the zero-
crossing signal of the 
variable fans

Another alarm situation occurs when power to 
the controller fails.  In this case, the alarm relay 
is activated.  When the alarm relay is activated, 
the normally open contact (

) closes.

12.1. Alarm Log

Select:

1. 

  Current Conditions (Main Menu) 

  Alarm Log

Alarm 

conditions

Details 

about 

the selected 

alarm

Alarm Log

 

Use   to navigate

  Logged at    Jan 01  200X
 

 

12:00  A

  Temperature 

High  °F

   Probe 5 Defective
   Probe 4 Defective

12.2. Alarm Conditions

Temperature Alarms

The diagram below shows how temperature 
alarms are detected.

When the average room temperature exceeds 
the  high  temperature  alarm  setting,  a  high 
temperature alarm is set off. When the aver-
age room temperature decreases below the 
low temperature alarm setting, a low tempera-
ture alarm is set off.  Although these settings 
are entered by the user as absolute values, 
they are defined based on the room set point. 
They are thus automatically adjusted if the 
set point changes. 

The  situation  is  slightly  different  when  the 
outside temperature is greater than the room 
set point. In this case, the outside tempera-
ture becomes the reference point (instead of 
using the set point as a the reference).  This 
means  an  alarm  is  set  off  when  the  room 
temperature  reaches  Outside  Temperature 
+  High  Alarm  Offset  (the  offset  being  the 
difference  between  the  high  alarm  tem-
perature setting and the set point). A third 
parameter,  called  the  critical  temperature, 
is defined to continue monitoring the indoor 
temperature for high temperatures. When the 
indoor temperature reaches the critical high 
temperature (defined as an absolute value), 
an alarm is set off.

Detection of 

Temperature Alarms

Room T°

Alarm 

Limits

Hi T° 

limit

Hi T° 

alarm

Lo T° 

limit

Set 

Point

Temperature Alarms in Clean Mode 

The controller can monitor low temperature 
alarms when it is in clean mode. If this alarm 
condition  is  used,  the  controller  sounds  an 
alarm when the temperature falls below low 
alarm  limit  that  is  associated  to  the  clean 
mode. 

The low alarm limit used in clean mode is re-
lated to the clean mode set point; this means 
the alarm limit is automatically adjusted when 
the clean mode set point changes.

Static Pressure Alarms 

The controller can sound an alarm when the 
static pressure (SP) level exceeds high or low 
pressure limits for a certain period of time. 

Feeder Alarm

The controller sets off an alarm if a feeder 
runs  continuously  on  a  too  long  period  of 
time.  When  this  type  of  alarm  occurs,  the 
relay associated with the problematic feeder 
opens in order to stop the feeder motor. This 
alarm condition is optional.

Missing Zero Crossing Alarm

If  the  zero-crossing  signal  of  the  variable 
output fails, the variable-speed fans will au-
tomatically  stop  running.  To  overcome  this 
problem, the controller can force these fans to 
restart running at full speed when this type of 
failure occurs: if the fan stage in use requries 
the  variable  fans  to  run  at  full  speed,  the 
controller will force the variable fans to stay 
on without interruption; if the stage asks for 
a variable speed, the controller will activate 
the variable-speed fans in timer mode (default 
timer = 30 seconds at 100% and 30 seconds 
Off). This zero-crossing timer can be modi-
fied by the integrator in the installation menu 
(factory password is required).

Содержание Koolmaster PP20-VS2

Страница 1: ...urtain 1 Close Inlet 2 Open Inlet 2 Close Inlet 1 Open Inlet 1 Close Stage 12 Stage 11 Stage 10 Stage 9 Stage 8 Stage 7 Stage 6 Stage 5 Stage 4 Stage 3 Stage 2 Stage 1 Min Vent Heater 1 Heater 2 Heater 3 Mist Soaking Kool Cel 0 10V 1 0 10V 2 Clock 1 Clock 2 PP 20 VS2 Variable 01 03 04 05 06 07 08 09 10 02 01 02 11 13 14 15 16 17 18 19 20 12 Read this guide carefully before using the controller ...

Страница 2: ...n be void if this product is used in a manner not specified by the manu facturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice due to further developments ...

Страница 3: ...ent 16 4 8 4 Night Settings 16 4 9 Clean Mode 17 4 10 Test Mode 17 4 11 Version 17 5 TEMPERATURE SETTINGS 18 5 1 Temperature Set Point 18 5 2 Temperature Curve 18 5 2 1 Principle of Operation 18 5 2 2 Settings 18 5 2 3 Modifying Curve Points 19 6 VENTILATION COOLING 19 6 1 Minimum Ventilation 19 6 1 1 Minimum Ventilation Cycles 19 6 1 2 Min Ventilation Settings 19 6 1 3 Minimum Ventilation Curve 2...

Страница 4: ...S 41 13 1 Current Conditions 41 13 2 History Menus 41 13 3 Animal Age Count 42 13 4 Automatic Reminder 42 14 TECHNICAL SPECIFICATIONS 43 15 MEMORY CARD 43 15 1 Principle of Operation 43 15 2 Accessing the Transfer Menu 43 15 3 Configuration Transfer 43 15 3 1 Installing a New Configuration 43 15 3 2 Saving a Configuration on the Card 44 15 4 Firmware Update 44 15 5 Erasing the Memory Card 44 16 IN...

Страница 5: ...ice on the controller s supply circuit The room temperature where the controller is located must always remain between 32 F and 104 F 0 C to 40 C Indoor use only To avoid exposing the controller to harmful gases or excessive humidity it is preferable to install it in a corridor If the equipment is used in a manner not specified by the manufacturer the protec tion provided by the equipment may be i...

Страница 6: ...monitor ing the sensor readings and verify the run time of some outputs The controller comes with the following histories menus Min Max sensor readings Room temperature 60 days Inside temperature sensors 10 days Outside temperature sensor 75 days Inside humidity sensor 75 days Outside humidity sensor 75 days Static pressure sensor 75 days Run time of each heater 75 days Run time of each feeder 75 ...

Страница 7: ...o 22 AWG wire to connect the devices to the 0 10V outputs This type of output can be used to connect various devices such as heat mats or fans 3 USER INTERFACE 3 1 Location of the Con trols Menu selectors Use these buttons to select a menu Current Condition short cut key This short cut key provides access to the main menu and allows seeing the current status of each input and output on the main sc...

Страница 8: ... Tunnel door 1 is closing CURTAIN 2 Open Solid LED Natural ventilation curtain 2 is opening Close Solid LED Natural ventilation curtain 2 is closing CURTAIN 1 Open Solid LED Natural ventilation curtain 1 is opening Close Solid LED Natural ventilation curtain 1 is closing INLET 2 Open Solid LED Inlet 2 is opening Flashing LED The controller opens inlet 2 to reset the actuator s position Close Solid...

Страница 9: ...The user is then identified If the installation password or user 2 pass 3 word is posted the prompt Change Password appears on screen Use the adjustment buttons to set the new password code Use the adjustment buttons to confirm the 4 new installer pas sword then press the right arrow key to confirm the new password 4 2 2 Retrieving a Lost Password Select 1 Current Conditions Main Menu Setup User P...

Страница 10: ...nabled in the Installation Setup are available see sec 4 5 The day number refers to the animal age 4 3 2 Copying Pasting Programs Use the copy paste function to duplicate all parameter settings associated to a program onto another program This avoids repeating the same programming sequence several times Select 1 Current Conditions Main Menu Setup Copy Paste A password may be required to access thi...

Страница 11: ...ila tion curtains 0 to 2 curtains Curtain Compensation Select Yes to en able a compensation on the opening of natural ventilation curtains as a function of the outside temperature Accessible if natural ventilation cur tains are enabled above and if an outside temperature sensor is enabled in sec 4 7 1 Number of Tunnel Doors Enable the proper number of tunnel doors 0 to 2 tunnel doors Use a Second ...

Страница 12: ...de Inlet 1 can either operate in timer mode or according to a potentiometer Select Pot to use a potentiometer or select Timer Note that the second inlet can only operate in timer mode Accessible if an inlet output is enabled above 0 10V type Select the type of signal used by each 0 10V output 0 10V or 10 0V Ac cessible if 0 10V outputs are enabled above 0 10V mode Select the function of each 0 10V...

Страница 13: ... Select Yes to let the controller adjust the bandwidth of stages 1 and 2 as a function of the outside temperature Available if the outside temperature probe is enabled see section 4 7 Number of programs The controller can use several temperature programs Enable the desired number of programs 1 to 3 programs Switch program by Age Out T The controller can automatically enable a new program when the ...

Страница 14: ...e this compensation method Mist Shutoff The controller can deactivate the misting output when humidity levels are too high Select Yes to use this compensa tion method Use Mist Shutoff The controller can ac tivate misting outputs when humidity levels are too low Select Yes to use this compen sation method Use Kool Cel Shutoff The controller can deactivate the Kool Cel output when humid ity levels a...

Страница 15: ...ams of the controller Probe Calibration Use to navigate Temperature Probe 1 0 0 F Temperature Probe 2 0 0 F Temperature Probe 3 0 0 F Temperature Probe 4 0 0 F Outside Probe 1 0 0 F Outside Probe 2 0 0 F Inside Humidity 0 Outside Humidity 0 Static Pressure 000 WC Water 1 Calibration 1 g p Water 2 Calibration 1 g p Water 3 Calibration 1 g p Adjust the reading of the probes 2 if required Temperature...

Страница 16: ...atus separately for each 2 fan stage in use Var The variable fan output is assigned to the fan stage and operates in variable mode when the stage starts the variable fan starts running at its minimum intensity The fan intensity gradually increases as the room temperature increases On The variable fan output is assigned to the fan stage and operates in on off mode the fan runs at 100 when the fan s...

Страница 17: ...ntroller operates in clean mode Clean mode status Select On to enable the clean mode select Off to disable it End of clean delay At the end of the clean mode the controller waits for a certain time before monitoring temperature alarms again Specify the time required for the room tem perature to get back to normal or select Off to disable this function decrease the param eter value until letters Of...

Страница 18: ... of 10 steps Each step specifies a day number and a temperature set point for that day the day number refers to the animal age Once the curve is activated the controller changes the set point every hour in a linear fashion between consecutive steps of the curve When the last step is reached the controller keeps using the tem perature set point associated to that day Set Point 90 0 87 2 84 4 81 6 7...

Страница 19: ...d to increase the minimum ventilation fan speed over time and another curve can be defined to increase the run time of the fans Refer to sec tion 4 5 to enable the Speed and or the On Time curve and refer to section 6 1 3 to define these curves Night fan speed If the nighttime minimum ventilation function is enabled section 4 10 you can select another minimum ventilation fan speed which will be us...

Страница 20: ...Off or ON Time Curve Program 1 Cur Day 5 day ON Time 60 sec day 1 20 sec day 10 22 sec day 15 24 sec Status Off Set the following parameters 2 The following parameters can only be modified while the curve is off If the min speed curve is running it is still possible to adjust the value of all curve steps simultaneously with the curve offset parameter see next section Current day This is the curren...

Страница 21: ...n of Variable Outputs Variable outputs are activated when their as sociated fan stage starts see section 4 9 They start running at their absolute minimum speed see section 4 5 and their speed gradually increases as the room temperature increases Variable outputs reach their full speed when the start temperature of the fol lowing fan stage is reached Transition between fan stages 1 and 2 If the nex...

Страница 22: ...s 0 3 F below the set point differential 1 the On Time value of the minimum ventilation cycle decreases gradually from a value equal to the total Cycle Time point C towards the regu lar On Time Ramping Settings To use the ramping function disable variable outputs in the Installation Setup section 4 5 and adjust the differential of stage 1 in section 6 2 2 Settings 6 2 2 6 2 2 1 Fan Stage Settings ...

Страница 23: ... T 0 10V Mode Automatic Manual You can manually control the intensity of a 0 10V output by using the manual control mode While this mode is used the control ler stops controlling the output and lets you choose the intensity of the output Select 1 Current Conditions Main Menu Start Stop 0 10V Select a 0 10V Ventilation output A password may be required to access this menu Accessible if a 0 10V vent...

Страница 24: ...Time Off Time when the tem perature falls below its closing temperature Natural ventilation is disabled when the average temperature decreases of 5 F 2 8 C below the curtain s closing temperature or when tun nel ventilation starts see graph below Using Tunnel Doors in Natural Ventilation When they are used in natural ventilation tunnel doors follow the same progression as natural ventilation curta...

Страница 25: ...ment Note that the initial tem perature of natural ventilation is limited by the start temperature of the last fan stage that belongs to the lateral ventilation mode power mode Start Close at Set the temperature below which the curtain starts closing in timer mode when the controller is in natural ventilation Start Open at Set the temperature above which the curtain opens according to a timer when...

Страница 26: ...radually opens the curtain as temperature rises in the room It can also disable a chosen selection of fans when the curtain is sufficiently opened when the curtain has reached its whisker switch When temperature falls point B on the graph At point B the curtain is already opened and the fans are stopped The controller gradually closes the curtain as temperature falls The controller restarts the fa...

Страница 27: ...rameters 2 First stage Both tunnel doors start opening when the start temperature of this fan stage is reached Select what fan stage signals the beginning of tunnel ventilation 100 opened Both tunnel doors fully open when the selected fan stage starts Select the fan stage at which tunnel doors are totally opened Probe set 2 starts at stage Select at what fan stage the controller starts measuring t...

Страница 28: ...sted when the reading of the inlet probes differs from the ambient temperature reading Refer to section 4 7 3 to assign probes to the air inlets The temperature compensation of the air inlet is expressed as a percentage per degree difference between the ambient temperature and the average reading of the inlet s probes It determines by how much an inlet must open or close to help reduce the tempera...

Страница 29: ...inlet according to this parameter value This parameter is accessible if the air inlet uses a timer It is also common to all programs Under Run Open Time Advanced parameter for timer based inlets only When a timer ends it may take a few seconds for the actua tor to actually stop moving For this reason the controller can switch off the actuator s motor slightly before its time for the actua tor to r...

Страница 30: ...Yes Save Maximum Position No Save minimum position 2 To calibrate the minimum position use the Close switch to close the inlet to its minimum position Once the inlet is closed set the manual con trol switch to Off to stop the actuator Now that the actuator is closed answer Yes to the Save minimum position question on screen Once the Yes answer is posted the controller switches the answer back to N...

Страница 31: ...of Kool Cels Kool Cel Output T inside or outside Off T Off On On T Principle of operation The Kool Cel output can either operate ac cording to the inside temperature or outside temperature it starts running in timer mode when the inside or outside temperature rises and reaches the output s start temperature the output stops when temperature falls below a user defined value It can also stop when hu...

Страница 32: ...utput starts Off temperature Select the temperature below which the misting output stops Minimum On Off times Set the on off times of the minimum misting timer Maximum Temperature Set the tempera ture at which the maximum misting timer if used Maximum On Off times Set the on and the off times of the maximum misting timer Start stop at Specify the period of time over which the output can run 6 9 St...

Страница 33: ...re Select Yes if you want to use the stir fan output in hot temperature conditions Cold temperature Select Yes if you want to use the stir fan output in cold temperature conditions Probe differential Select Yes if you want to use the stir fan output to reduce tempera ture differences between probes Hot start stop temperature If stir fans are used in hot temperature conditions set the room temperat...

Страница 34: ...Hi Lo fire option is used set this temperature sepa rately for both steps of the heating stage In addition if the night heater offset is enabled in section 4 8 4 these parameters must be set separately for day night Off temperature Set the temperature at which each heating stage stops Note that the Off Temperature of an heating stage must be at least 0 5 F 0 3 C higher that its On Temperature If t...

Страница 35: ...mpera ture to the desired value Note that this tem perature can be set as a fix value absolute or it can be related to the set point this means that when the set point changes the start temperature is adjusted by the same amount refer to section 4 5 to specify if the start temperature of the 0 10V follows the set point or not 0 10V Output X Heat Lamp Mode Automatic Current Output 0 Start Temperatu...

Страница 36: ...ither stops after a certain run time or at a certain time of day The fol lowing diagrams show both possibilities Time Cycle Output Status On Start Time e g 8h30AM Time Clock Start Stop Mode Stop Time e g 9h00AM Off Time Output Status Cycle Start Time e g 8h30AM Time Clock Start Run Mode Run Time e g 30m 15s On Off Select 1 Current Conditions Main Menu Start Stop Clocks Clock x A password may be re...

Страница 37: ...e for the change The maximum compensated On Time is reached when the RH level is 10 above the RH set point RH Compensation on Minimum Ventilation RH Level 10 RH Set Point Off Regular On Time Compen sated On Time On Time of the Min Vent timer Added Time RH Comp on the Fan Speed RH level Fan Speed V1 Speed RH Set Point V1 regular speed V2 initial speed V1 added speed V2 added speed Compen sated spee...

Страница 38: ...ed is specified above for variable output 2 Heater compensation Minimum Maximum On Times Set the minimum and maximum On Times of the heating timer The minimum On Time starts being used when indoor humidity levels reach the RH set point the maximum On Time is used when humidity levels are 10 above the RH set point Accessible if RH compensation with heating outputs is enabled in section 4 6 Cycle Ti...

Страница 39: ...ettings are entered by the user as absolute values they are defined based on the room set point They are thus automatically adjusted if the set point changes The situation is slightly different when the outside temperature is greater than the room set point In this case the outside tempera ture becomes the reference point instead of using the set point as a the reference This means an alarm is set...

Страница 40: ...ter meter is enabled sec 4 7 1 Refer to the previous section to get more information about this alarm limit Reset Alarm If a high or low water consumption alarm is on select Yes to acknowledge the alarm condition Note that when a reset is made the controller needs 48 hours to gather new consumption data be fore it can start monitoring the high low water consumption alarms again no consumption alar...

Страница 41: ...ble module failure Alarm conditions that activate the alarm relay are common to all programs 13 2 History Menus History menus give a daily record of probe readings and of the animal count These pieces of information are logged into history menus at midnight Refer to section 13 2 to consult run time histories for heaters water consumption and feeders Select 1 Current Conditions Main Menu History Se...

Страница 42: ...can specify the number of mortalities culled and marketed animals as it occurs ALL histories of the controller all water consumption data are reset when a new group starts Select 1 Current Conditions Main Menu Age Mortality Accessible if age based functions are enabled in the Installation Setup section 4 5 Age Mortality Animal Age 4 day Initial Count 1200 Current Count 1200 Start New Group No Sele...

Страница 43: ...onnector 2 located on the electronic board located on the back of the front panel see illustration Close the front panel then simultaneously 3 press the up and down arrow keys for 3 sec onds to display the transfer menu Select the desired transfer menu 4 Current Conditions Main Menu Memory Card Controller or Controller Memory Card Configuration Transfer 15 3 Configuration Files cfg Configuration f...

Страница 44: ...Press and hold the up and down arrow 2 keys simultaneously for 3 seconds The Firmware Update menu is displayed Controller to Memory card Next Exit Use to navigate WARNING It is extremely important to ensure that the AC power source is not interrupted during this process This unit may render inoperable if power fails during this update To continue this process press NEXT Read the warning message ca...

Страница 45: ... use 41 Minimum ventilation See Minimum ventilation Principle of operation 21 Relay assignment 15 Settings 22 23 Timer relays Principle of operation 21 Timer settings 22 Transition between stages 1 and 2 Principle of operation 21 Settings 22 Variable fans Activation 11 Assignment 16 Current speed of the fans 41 Minimum fan speed 12 Principle of operation 21 RH Compensation on fan speed 14 37 38 Fa...

Страница 46: ...ion 37 Settings 38 RH set point 38 Relay panel 12 Relays Alarm relay 41 Relay assignment Clearing the assignment 13 Making the assignment 15 Shutoff fan relays in natural ventila tion Principle of operation 26 Relay selection 16 Timer relays Principle of operation 21 Timer settings 22 S Screens LED LCD 7 Sensors See Probes Set points RH set point See Relative humidity Temperature set points 18 Set...

Страница 47: ......

Страница 48: ...REV 00 M 890 00527 rev 00 ...

Отзывы: