Example 3 – AI128 returns a value of 42 representing AI28 (Lost
Communication), BV08 (Lost Communication) & AV08 (Lost
Communication).
-
Example 4 – AI128 returns a value of 9 representing AI28 (Low
Battery Alarm), BV08 (Lost Communication) & AV08 (Normal).
The MOD9200BNT Device Instance and MSTP MAC address will be
preset from the factory and can be obtained using the BACnet Device
Scan function. To ensure no duplication of Instance/address, verify
that no other node with the same address is present at the sub-net
where the MOD9200BNT will be residing.
For more implementation information please refer to the BACnet website
www.BACnet.org
or the ASHRAE (American Society of Heating, Refrigeration
& Air-conditioning Engineers) website www.ashrae.org.