MOD9000BNT BACnet Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000674
Middleton, Wisconsin 53562
Page 8 of 37
www.workaci.com
(888) 967-5224
d.
Manually Resetting The Factory Default IP Address
The Transceiver can manually be reset to the default IP Address by moving the jumper
(J6) from “Norm” to “Init”.
Turn off the power to the Transceiver, and move the jumper from “Norm” to “Init”. Turn
on power, and the Transceiver can be communicated with using the Factory Default IP
Address 192.168.0.1 Subnet Mask 255.255.255.0. The Config File is no longer active
while the jumper is in the “Init” position . A new Config File can be downloaded to the
Transceiver if desired.
To reactivate the Config File - turn off the power to the Transceiver and move the jumper
back to “Norm”. Turn the power back on and the Config File will become active. The
Transceiver will have the IP Address that was set in the Config File.