Input Register Configuration
Each row of the configuration table is a unique data register having eight
special attributes.
REG FUNCTION
-- Identifies the function of the register – Analog or Digital
(Discrete) Note: If selecting the Digital (Discrete) function
be sure to set the appropriate Digital Capture Time (Page 15)
REG ADDRESS
-- Assigns the address of the data register (0 to 99).
GROUP NAME
-- Assigns a group name to the data register (not used by
BACnet). Multiple data registers can have the same group
name. This is useful for monitoring and data logging
programs.
POINT NAME
-- Assigns a unique name to the data register to help identify
the location of the sensor/transmitter (Not used by BACnet).
Multiple point names can have the same group name.
TRANSMITTER ID
-- Assigns a wireless sensor/transmitter address to the data
register. Each wireless sensor is factory configured with a
unique hexadecimal address.
TRANS CHAN
-- Assigns a wireless sensor/transmitter data channel to the data
register. A wireless sensor/transmitter may have up to four
(4) analog channels and (4) digital status/alarm channels.
DATA FORMAT
-- Assigns the data type to the register – temperature (RTD or
Thermistor 20K), analog voltage, totalizer or humidity. This
register is left blank if the REG FUNCTION is Digital
(Discrete).
LOG
-- Not used for MOD9200LON
First we will assign the REG FUNCTION by clicking in the REG
FUNCTION cell to open a drop down menu. Select the appropriate function.