MOD9000BNT BACnet Receiver Installation & Configuration

 

 

AUTOMATION COMPONENTS, INC                                                                                                                                                                 Version : 1.0  
2305 Pleasant View Road                                                                                                                                                                                        I0000674 
Middleton, Wisconsin 53562                                            

                        Page 32 of 37                                       

www.workaci.com

   (888) 967-5224                                                                                                                                                        

 

the remote unit executed the command issued by the MOD9200, It will 
send a feedback status of the analog output value to the MOD9200. 

 

The AI101 through AI200 Objects are the alarm registers for all the input 
and output data points (AI01-100, BV01-50 and AV01-50). Each point 
utilizes 6 binary bits of information representing the alarm conditions of 
the “Input Registers/AI Object”, “Digital Output (Coil) Register/BV 
Object” and “Analog Output (Holding) Register/AV Object”. 
 

 

 

The Present Value of each register displays a decimal value representing 
the alarm status of all 3 point types. Each point type returns an individual 
alarm value in decimal format. All 3 point types decimal values are added 
together to represent the status of the 3 alarm status. 

 

The decimal values of different point types are: 
-

 

The Input Register/AI Object alarms 

 

“0”= Normal 

 

“1”= Low Battery Alarm (Bit 1 set) 

 

“2”= Lost Communication Alarm (Bit 2 set) 

 

-

 

The Digital Output (Coil) Registers/BV Object alarm 

 

“0” Normal 

 

“8”= Lost Communication Alarm (Bit 4 set) 

 

-

 

The Analog Output (Holding) Registers/AV Object alarm 

 

“0” Normal 

 

“32”= Lost Communication Alarm (Bit 6 set) 

 

Alarm Status Examples: 

 

-

 

Example 1 – AI108 returns a value of 33 representing AI08 (Low 
Battery Alarm), BV08 (Normal) & AV08 (Lost Communication). 

 

-

 

Example 2 – AI108 returns a value of 40 representing AI08 
(Normal), BV08 (Lost Communication) & AV08 (Lost 
Communication). 

000000

AI Object
(Bit 1 & 2)

BV Object
(Bit 3 & 4)

AV Object
(Bit 5 & 6)

Содержание MOD9200BNT

Страница 1: ...User s Manual MOD9200BNT BACnet Transceiver Configuration Software Setup Configuration ...

Страница 2: ...FOR THE LIMITED WARRANTY ABOVE THE PRODUCT IS PROVIDED AS IS TO THE MAXIMUM EXTENT PERMITTED BY LAW ACI DISCLAIMS ALL OTHER WARRANTIES OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ACI DOES NOT WARRANT THAT THE FUNCTIONS CONTAINED IN THE PRODUCT WILL MEET ANY REQUIREMENTS OR NEEDS YOU MAY HAVE OR THAT...

Страница 3: ...9 a Configuration Software Description 9 b System Requirements 9 c Configuration Software Installation 9 d Creating A MOD9200 Configuration File 10 e Input Register Configuration 11 f Digital Output Coil Register Configuration 15 g Analog Output Holding Register Configuration 18 h Setting the Mesh Network ID for the repeater router devices 20 i Miscellaneous Menu 21 j Configuring The Transceiver F...

Страница 4: ...and status alarm indications to a centralized networked monitoring station or controller without the need for extensive wiring The MOD9000BNT is compatible with any control panels or automation systems that utilize the BACnet MSTP communication protocol a ACI MOD9200 Transceiver System MOD9200BNT BACnet MSTP Network Transceiver Receives input from up to 50 remote wireless sensor modules and or wir...

Страница 5: ...ect 24VAC 60 Hz no secondary ground to the input terminals using 20 AWG wire as shown in the product data sheet Figure 1 MSTP RS485 Use 20 gauge shielded twisted pair wire to connect the Transceiver Terminals A B to the network See Figure 1 Multiple RS485 Devices If more than one RS485 device is used the devices should be daisy chained or straight line connected by connecting all the A wires to th...

Страница 6: ...the Transceiver for transporting the Transceiver Configuration File via FTP Connect the MOD9200 Transceiver J2 to a 10 100Base T Ethernet network or use a crossover cable to connect directly to the PC Apply 24 VAC 60 Hz power to the MOD9200 Transceiver c Setting A New IP Address The MOD9200 is shipped from the factory with an IP address of 192 168 0 1 and a subnet mask of 255 255 255 0 Note To ini...

Страница 7: ...and Subnet Mask and click OK The new IP Address will take affect when the Config File is downloaded to the Transceiver Our recommendation is not to change the default factory IP address of the transceiver since the Ethernet connection is used to configure the transceiver only and will not be required when the MSTP network is up and running Router Setup Webserver Only NOT USE Applicable for RM9500 ...

Страница 8: ... to the Transceiver and move the jumper from Norm to Init Turn on power and the Transceiver can be communicated with using the Factory Default IP Address 192 168 0 1 Subnet Mask 255 255 255 0 The Config File is no longer active while the jumper is in the Init position A new Config File can be downloaded to the Transceiver if desired To reactivate the Config File turn off the power to the Transceiv...

Страница 9: ...sters as follows Assign the Input Register function Analog or Discrete Assign wireless Digital Output Coil Register function Assign wireless Analog Output Holding Register function Assign the register address Assign the Wireless Sensor ID and transmission channel Assign the data type The MOD9200 Transceiver can have up to 100 addresses 0 to 99 data registers configured to be either Analog or Discr...

Страница 10: ... new MOD9200 configuration file open the ACI Programmer by clicking on Start Programs Trs Programmer 6 XX To open a new configuration table Click on File New Gateway File A blank configuration table will open The default startup is the Input Register configuration table and System Setup page By clicking the RegisterBank tab you can go to the Digital Output Coil register configuration table or Anal...

Страница 11: ...r monitoring and data logging programs POINT NAME Assigns a unique name to the data register to help identify the location of the sensor transmitter Not used by BACnet Multiple point names can have the same group name TRANSMITTER ID Assigns a wireless sensor transmitter address to the data register Each wireless sensor is factory configured with a unique hexadecimal address TRANS CHAN Assigns a wi...

Страница 12: ... is turned off as shown Enter the Register address in the REG ADDRESS window and press down arrow to enter Again use the mouse to move to the next column Enter a GROUP NAME for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Group Name Enter a POINT NAME for the data point by typ...

Страница 13: ...ar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the drop down menu Each ACI wireless transmitter is factory configured with a unique ID refer to the sensor product data sheet for the location of the transmitter ID Assign the appropriate sensor transmission channel to the da...

Страница 14: ...mp Therm 20K Humidity OA2630A Outdoor Temp Therm 20K Outdoor Humidity OST2630A Outdoor Temp Therm 20K DT2630A Duct Temperature Therm 20K DT2650A Ave Temperature Therm 20K DH2630A Duct Humidity DH2630B Duct Temperature Therm 20K Duct Humidity FT2630A Fluid Temperature Therm 20K RT2630A B C See Device Label for Analog 4 and Digital 4 Configuration RT2620A See Device Label for Digital 4 Configuration...

Страница 15: ...e to do this for each row data register that needs to be configured The completed configuration example for an office building is as follows The columns may be resized by placing the cursor over one side of the column When the cursor changes to two arrows hold down the left mouse button and drag the side of the column to resize it f Digital Output Coil Register Configuration Select the Digital Out...

Страница 16: ... in the cell Before entering register addresses ensure the RegisterEntry AutoSet is turned off as shown Enter the Register address in the REG ADDRESS window The valid range is 0 to 49 Again use the mouse to move to the next column Enter a GROUP NAME if desired for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT...

Страница 17: ...e Point Name Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu This is the device ID of the remote output devices RD2402 RD2432 Use the scroll bar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the drop down menu ...

Страница 18: ...ay 1 and relay 2 NA Wireless relay output module RD2432 1 to 4 for relay 1 to relay 4 1 to 4 for analog output 1 to 4 Wireless digital analog output module g Analog Output Holding Register Configuration Select the Analog Output Holding Register table by clicking the RegisterBank tab First we will assign the REG ADDRESS by clicking in the cell Before entering register addresses ensure the RegisterE...

Страница 19: ...s or semicolons in the Group Name Enter a POINT NAME if desired for the data point by typing the name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Point Name Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu This is the device ID of the remote output d...

Страница 20: ... active transmission channels or output number are factory set as follows Device Digital Analog RD2402 1 to 2 for relay 1 and relay 2 NA Wireless relay output module RD2432 1 to 4 for relay 1 to relay 4 1 to 4 for analog output 1 to 4 Wireless digital analog output module h Setting the Mesh Network ID for the repeater router devices The mesh network ID of the MOD9200 Gateway can be set to specific...

Страница 21: ...re set globally for all sensors using the Miscellaneous Dialog Screen Click on Settings Miscellaneous Set the transmitter transmission timeout interval requires a minimum of 30 min by clicking in the Transmitter Timeout cell to open a drop down menu Use the scroll bar to scroll down to the appropriate value 1 to 60 min or type the value in the cell to automatically scroll to the appropriate value ...

Страница 22: ...eeded such as unoccupied period by pass Set the Digital Capture Time interval seconds or minutes by clicking on Seconds or Minutes Click in the Digital Capture Time cell to open a drop down menu Use the scroll bar to scroll down to the appropriate value 0 to 240 or type the value in the cell to automatically scroll to the appropriate value To select the timeout interval click on the appropriate va...

Страница 23: ...ransceiver For MSTP RS485 Network The Transceiver needs to be assigned an Identifier Address for device internal use To enter the Transceiver Unit ID into the Configuration File click on the Menu Comm Unit Identifier Click on the drop down menu arrow and select the Transceiver Unit Default ID of 1 from the drop down menu and click OK Click on Menu Comm Serial Transport to activate the Serial Comm ...

Страница 24: ...Connect Speed Connect Preferences and Transport Mode for the Transceiver The MOD9200BNT requires internal communication parameters to be set as follows Maximum Speed 38400 BPS This communication speed is set for internal use by the MOD9200BNT Transceiver and it will not change the external BACnet MSTP communication speed of 76800BPS Data Bits 8 Parity none Stop Bit 1 Modbus Transport RTU The MOD92...

Страница 25: ...e the configuration file click on File Save It is recommended that the cfg file be saved in the Trs folder already setup i e C trs config k Sending The Configuration File To The MOD9200 Before sending the file to the MOD9200 it is important to ensure that the Serial Transport setting is checked as shown Always save the configuration file to the folder trs before sending it to the MOD9200 Transceiv...

Страница 26: ...age 26 of 37 www workaci com 888 967 5224 To send the new configuration file to the MOD9200 Transceiver click on File File Transfer and a dialog box will appear Click on Select File and a window will open Move to the Trs directory and select the appropriate file from the list Click on Open to automatically enter the selected file path as the File Name ...

Страница 27: ... of 37 www workaci com 888 967 5224 Enter the current IP Address of the Transceiver Note This can be different than the IP Address entered into the configuration file Click on Connect and the status of the connection will be displayed in the Comm Status window When the Transceiver is connected click on Send File to the send the config file to the Transceiver ...

Страница 28: ...fig file To confirm that the appropriate configuration file is saved on the Transceiver reopen the File Transfer Dialog and click on Get File to retrieve a copy of the active configuration file from the Transceiver The Editor will automatically save this file in the folder trs with the file name of _config ini Click on File Open Config File and select the _config ini file Click on Open to open the...

Страница 29: ... View Road I0000674 Middleton Wisconsin 53562 Page 29 of 37 www workaci com 888 967 5224 NOTE The _config ini file is a dynamic file If multiple MOD9200 Transceivers are being administered from the same PC the _config ini file will be a copy of the configuration file from the last Transceiver administered ...

Страница 30: ...P Master Slave Token Passing relies on the EIA 485 serial communication signaling standard o BACnet PTP point to point For temporary connections between Devices b MOD9200BNT BACnet Transceiver Parameters The MOD9200BNT Transceiver BACnet MSTP device communicating at 76800BPS It receives data from up to fifty 50 wireless sensors and updates its data registers on a real time basis BACnet Object Type...

Страница 31: ...ns again The Present Value of BV01 through BV50 objects will correspond to the MOD9200 Digital Output Coil Register 0 through 49 For BVXX XX Trs MOD9200 Register Num 1 The BV01 to BV50 Objects are used for command remote wireless digital outputs relays module i e ED2402D the SD2432D devices Values to be entered or sent is 1 on and 0 off The BV51 through BV100 Objects will be automatically assigned...

Страница 32: ...ys a decimal value representing the alarm status of all 3 point types Each point type returns an individual alarm value in decimal format All 3 point types decimal values are added together to represent the status of the 3 alarm status The decimal values of different point types are The Input Register AI Object alarms 0 Normal 1 Low Battery Alarm Bit 1 set 2 Lost Communication Alarm Bit 2 set The ...

Страница 33: ...resenting AI28 Low Battery Alarm BV08 Lost Communication AV08 Normal The MOD9200BNT Device Instance and MSTP MAC address will be preset from the factory and can be obtained using the BACnet Device Scan function To ensure no duplication of Instance address verify that no other node with the same address is present at the sub net where the MOD9200BNT will be residing For more implementation informat...

Страница 34: ...atic IP address of 192 168 0 X X can be any number except 1 or 2 with a subnet mask of 255 255 255 0 5 Installing The MOD9200 Configuration Software 6 Configure the MOD9200BNT Transceiver b Installing the MSTP RS485 Network 1 Choose a location close to the computer or RS485 loop 2 Mount the Transceiver on the wall using four 8 screws 3 MSTP RS485 Use 20 gauge shielded twisted pair wire to connect ...

Страница 35: ... 20 AWG wire as shown in the product data sheet 7 Power up the MOD9200 Transceiver with the BACnet MSTP network 8 Use BACnet Device Scan function to identify the MOD9200 Device Instance MSTP address 9 Verify there is no address conflict with other node in the subnet 10 Proceed to read object AI01 to AIXX AI101 to AI1XX alarm property where XX is the last data register configured using the Trs Prog...

Страница 36: ...OMATION COMPONENTS INC Version 1 0 2305 Pleasant View Road I0000674 Middleton Wisconsin 53562 Page 36 of 37 www workaci com 888 967 5224 For more information please contact ACI 2305 Pleasant View Rd Middleton WI 53562 Telephone 1 608 831 2585 www workaci com ...

Страница 37: ...OFF 8 OFF ON OFF ON OFF OFF OFF OFF 80 OFF ON OFF ON OFF OFF OFF ON 81 OFF ON OFF ON OFF OFF ON OFF 82 OFF ON OFF ON OFF OFF ON ON 83 OFF ON OFF ON OFF ON OFF OFF 84 OFF ON ON ON ON ON OFF OFF 124 OFF ON ON ON ON ON OFF ON 125 OFF ON ON ON ON ON ON OFF 126 OFF ON ON ON ON ON ON ON 127 Network Node or Instance Address Setting from Node 1 to Node 127 maximum Baud Rate Switch B4 Switch B3 Switch B2 S...

Отзывы: