background image

9

Then run the vacuum pump.

The  running  time  varies  depending  on  the  length  of  the  pipes 

andthe capacity of the pump.

When the desired vacuum is reached, close the “LOW” knob of 

the pressure gauge valve and stop the vacuum pump.

Finally,  using  a  service  valve  wrench,  turn  the  gas  side  valve 

stem counterclockwise to fully open.

Loosen the charging hose connected to the gas side service port 

to relieve the pressure, then remove the hose.

Replace  the gas  valve  and  service  plug  cover  nut and  tighten 

securely with an adjustable wrench.

This procedure is very important to avoid system leaks.

Replace the service valve caps on both the gas and liquid side 

and tighten well. This completes the air purge procedure with the 

vacuum pump, make sure that all pipes are connected correctly 

and  that  the  service  valves  on  the  gas  and  liquid  sides  are 

completely open.

3.6 OPENING THE VALVES AND RELEASING THE 

REFRIGERANT RELATING TO THE OUTDOOR UNIT

1)  Remove the cap of the liquid sectioning valve coolant, liquid

 

side (Fig. B n. 1).

2)   Open valve A with the aid of a hex wrench turning

 

anticlockwise until it stops (Fig. B n. 2).

3)   Replace the cap.

4)   Remove the cap from the gas cut-off valve coolant (Fig. B n. 4).

5)   Open the valve with pliers by turning counterclockwise of a

 

quarter of a turn (Fig. B n. 5).

6)   Replace the cap.

7)   Disconnect the vacuum gauge and the vacuum pump.

8)   Put the cap back on the valve (Fig. B n. 3).

9)   Tighten all the caps with the aid of a torque wrench with

 

tightening torque from 20 to 25 N / m. See table 3.

10)  Check the tightness of the fittings using a leak detector

1

8

3

2

5

4

6

Fig. B

Gas side cock

Liquid side tap

3.7  PUMP DOWN

This procedure is carried out when the unit needs to be moved or 

assistance is carried out on the refrigerant circuit.

Emptying allows all the refrigerant to be collected in the outdoor 

unit without leaks.

3.8 RECOVERY PROCEDURE

-  Connect a low pressure gauge with a hose to the gas valve

  service socket.

-   Half open the gas valve and empty the air from the pipeline

  pressure gauge using refrigerant gas.

-   Close the liquid valve completely.

-   Turn on the machine in cooling mode.

-   When the pressure of the manometer goes between 0 and 0.5

  kg / cm 2G (between 14.2 and 7.1 P.S.G.I) close the valve

  completely gas and quickly turn off the indoor unit.

  Complete recovery of the refrigerant from the outdoor unit was

  thus carried out.

ATTENTION! Be sure to perform the emptying procedure 

with the unit in COLD MODE.
3.9 ACOUSTIC REQUIREMENTS (Fig. 11)

During  the  installation  phase  of  a  HUB  RADIATOR  MINI  heat 

pump,  it  is  necessary  to  evaluate  very  carefully  where  the 

outdoor unit is positioned, in order to avoid induced noise that 

goes beyond the tolerance threshold.

on the ground, free instal 3 dB (A)

in a corner of the recessed 9 dB (A)

against the 6 dB (A)

Fig. 11

POSITIONING OF THE

OUTDOOR UNIT

The external evaporating motor unit during work generates external 

noise emissions and requires appropriate measures to reduce the 

incidence of noise produced by the compressor and / or fan.

Very important then is the system execution that is combined with 

the heat pump in this regard it is recommended to use the following 

accessories  listed  below  (see  Chapter  4.9 ACCESSORIES  HUB 

RADIATOR MINI XL)

ANTI-VIBRATION FLOOR BASE IN VULCANIZED RUBBER 

(HEIGHT FROM THE GROUND MM 95) WITH LEVEL AND 

SCREWS FOR BOOSTER HR 3.0 - 7.8 - 9.0

ANTI-VIBRATION KIT FOR INSTALLATION ON SHELVES

Содержание HUB RADIATOR MINI 11.0

Страница 1: ...L Patented high efficiency direct coolant water exchange to produce domestic hot water and heating for small and medium sized users HUB RADIATOR MINI XL INSTALLATION MANUAL FIRST START UP MANDATORY FO...

Страница 2: ...n the last page The entry into force of new provisions or changes to those in force will not constitute a reason for any obligation of the A2B Accorroni E G S r l towards third parties The A2B Accorro...

Страница 3: ...B RADIATOR MINI XL 16 0 32 9 MINI XL RADIATOR HUB CIRCULATOR 33 10 DIVERTER VALVE HUB RADIATOR MINI XL 33 11 ELECTRIC RESISTANCE MINI XL 33 12 WARNINGS 33 12 1 Qualification of the installer 33 12 2 P...

Страница 4: ...nternal copper exchangers auxiliary back up and emergency supplementary resistor refrigerant gas connections DHW air siphon jolly valve safety valve filling cock pressure gauge diverter valve to give...

Страница 5: ...e outdoor unit 4 Remove the cover of the outdoor unit 5 Connect the terminal cables according to the numbers on the unit terminal block respecting the sections shown in table 1 6 Secure the cables so...

Страница 6: ...ple A of table 4 B INSTALLAZIONE CON LUNGHEZZAMINIMAAMMISSIBILE Qualora la distanza tra le unit Unit Interna ed Unit Esterna sia inferiore a 3 metri come in questo caso dove la lunghezza delle tubazio...

Страница 7: ...base equipped with appropriate anti vibration bearings to avoid the increase of vibrations e noise so as not to disturb neighbors Fig 7 Fig 7 Position the air outlet so that the flow is not hindered...

Страница 8: ...ing elements and moisture from the system Check that each pipe both the gas and liquid side pipes between the internal and external groups has been connected correctly and that all the wiring required...

Страница 9: ...quid side tap 3 7 PUMP DOWN This procedure is carried out when the unit needs to be moved or assistance is carried out on the refrigerant circuit Emptying allows all the refrigerant to be collected in...

Страница 10: ...irculator 4 Automatic filling group 5 Manual filling taps 6 System pressure gauges with 1 4 connections 7 Safety valve with 3 bar calibration and max pressure 10 bar 8 Diverter valve with 3 4 connecti...

Страница 11: ...em heat dispersion G Connect a special safety drain at the 1 2 female threaded connection of the safety valve H Make the electrical connections between the electrical panel and the main power supply a...

Страница 12: ...alve 4 Male threaded connection SAE cooling line 1 4 R410A Booster 1 5 Male threaded connection SAE cooling line R410A 5 8 or 3 8 Booster 1 6 Male threaded connection SAE cooling line 1 4 R410A Booste...

Страница 13: ...3 48 3 57 3 67 3 78 3 88 4 00 4 11 4 20 4 35 4 47 4 60 4 73 4 86 5 00 5 15 5 29 40 2 25 2 32 2 39 2 47 2 54 2 62 2 70 2 78 2 86 2 94 3 02 3 11 3 20 3 29 3 38 3 47 3 57 3 66 3 76 3 86 3 97 4 08 4 19 4...

Страница 14: ...3 18 3 28 3 37 3 47 3 62 3 67 3 77 3 88 3 99 4 14 4 25 4 36 4 50 4 62 4 74 4 87 5 02 5 15 40 2 18 2 25 2 33 2 40 2 47 2 55 2 62 2 70 2 78 2 86 2 94 3 02 3 10 3 19 3 28 3 37 3 46 3 56 3 65 3 75 3 86 3...

Страница 15: ...O P 1 Thermal power 2 Absorbed power 2 C O P 2 Thermal power 3 Absorbed power 3 C O P 3 Thermal power 4 Absorbed power 4 C O P 4 Thermal power 5 Absorbed power 5 C O P 5 Thermal power 6 Absorbed powe...

Страница 16: ...ANTI VIBRATION KIT FOR INSTALLATION ON SHELVES ANTI VIBRATION FLOOR BASE IN VULCANIZED RUBBER HEIGHT FROM THE GROUND MM 95 WITH LEVEL AND SCREWS FOR BOOSTER HR 3 0 7 8 9 0 COMPLETE STAINLESS STEEL SP...

Страница 17: ...dary display yellow color display configurable by parameter CF43 PB1 PB2 PB3 PB4 Set point from parameter Real set point Hysteresis RTC Machine status the display shows the chiller set when the unit i...

Страница 18: ...of parameters Parameter being edited increases its value Press and release from main view allows the display of the probe values configured temperatures pressures in the upper display and the label co...

Страница 19: ...zer the expected range Flashing icon generic alarm Code on display P4 Probe alarm Probe faulty our Activate output open Automatic PB4 resistive value collector rel alarm if the value is within out of...

Страница 20: ...l Booster Charging alarm thermostat 3 Q E thermostat connection 3 Replacement of the Q E contact open thermostat connection cable A12 Defrost End defrost 1 Lack of refrigerant gas 1 External Booster C...

Страница 21: ...escrizione min max udm Risoluzion e ST18 Set point ambiente in chiller ST20 ST21 C F dec int ST19 Differenziale ambiente in chiller 0 0 0 25 0 45 C F Dec int ST20 Set minimo ambiente in chiller 50 0 5...

Страница 22: ...ttivo contatto chiuso 1 Attivo contatto aperto 0 1 12 Allarme termica pompa acqua evaporatore termica ventilatore di mandata 13 Allarme termica pompa acqua condensatore 14 Flussostato condensatore 15...

Страница 23: ...Funzionamento continuo in uscita 4 20mA 4 Funzionamento su chiamata del compressore 4 20mA 0 4 CO12 Compressore 1 0 Abilitato 1 OFF 0 1 CO13 Compressore 2 parzializzazione 0 Abilitato 1 OFF 0 1 CO14...

Страница 24: ...abilitato 1 Abilitato 0 1 dF17 Ritardo allarme di minima all inversione della valvola 4 vie 0 250 Sec FA09 Massima velocit ventole in estate 30 100 FA10 Set temperatura pressione minima velocit vento...

Страница 25: ...el allarme uscita open collector 0 Uscita senza tensione in condizioni normali con tensione in presenza di allarme 1 Uscita con tensione in condizioni normali senza tensione in presenza di allarme 0 1...

Страница 26: ...Umin 80 T 8 s OK U Umin U Umax Before making connections make sure you have correctly sized the section of the power cables based on the actual distance from the counter Always provide for a special o...

Страница 27: ...27 7 2 WIRING DIAGRAM HUB RADIATOR MINI XL 6 0...

Страница 28: ...28 7 3 WIRING DIAGRAM HUB RADIATOR MINI XL 8 0...

Страница 29: ...29 7 4 WIRING DIAGRAM HUB RADIATOR MINI XL 11 0...

Страница 30: ...30 7 5 WIRING DIAGRAM HUB RADIATOR MINI XL 16 0...

Страница 31: ...31 Marrone Nero Blu 7 6 WIRING DIAGRAM HUB RADIATOR MINI XL 24 0...

Страница 32: ...ulation pump 30 Refrigeration line R410A 1 4 liquid 31 5 8 R410A refrigeration line gas 32 Base support as standard 6 7 8 9 24 18 10 11 17 16 13 15 14 1 30 30 31 31 1 5 22 23 23 32 2 29 2 3 25 26 28 3...

Страница 33: ...s are equipped with a motorized diverter valve with spring return The diverter valve is powered and automatically diverts to the system when the temperature of the technical storage exceeds 47 C param...

Страница 34: ...pipes Do not allow the power cables to come into contact with pipes Install zone motorized valves in the system to prevent the water contained in the accumulation not circulate freely when it is not...

Страница 35: ...at least 30 minutes 14 3 CLEANING THE CIRCUIT ATTENTION If the motor burns with perforation of the windings it is necessary to carefully clean the refrigerant circuit to avoid subsequent burns or bre...

Страница 36: ...r switching on and 16 for switching off ATTENTION In all cases described below in which the programmer gives consent to start the actual operation of the radiator is however also affected by the adjus...

Страница 37: ...el on both axes Presence of anti vibration mounts between the outdoor unit and the ground or shelf Check the safety distances indicated in the manual Distance between indoor and outdoor unit max 15m a...

Страница 38: ...______________________________________________________________________________ _________________________________________________________________________________________________________________________...

Страница 39: ...s INDOOR UNIT OUTDOOR UNIT Failure to comply with this application will result in the non ignition by the authorized assistance Attached A Attached B 6 m 4 m INDOOR UNIT OUTDOOR UNIT INSTALLATION NOT...

Страница 40: ...__________ ________________ _______________ ________________ ______________ ___________ ________________ POSITIONING THE OUTDOOR UNIT TO THE GROUND WALL A WINDOW ON BRACKETS ANTI VIBRATION SHELVES ROO...

Страница 41: ...rte superiore del compressore a circa 8 cm di distanza dalla calotta FUNZIONAMENTO IN POMPA DI CALORE BOOSTER 3 TEMPERATURA DI EVAPORAZIONE U E C Pb3 _______ TEMPERATURA ACQUA TECNICA C Pb1 _______ NB...

Страница 42: ...pe that comes out from the top of the compressor about 8 cm away from the hood OPERATION IN BOOSTER HEAT PUMP 3 EVAPORATION TEMPERATURE O U C Pb3 _______ TECHNICAL WATER TEMPERATURE C Pb1 _______ ATTE...

Страница 43: ...STOMER INSTALLER TECHNICAL ASSISTANCE CUSTOMER SIGNATURE SIGNATURE SIGNATURE _____________________________ _____________________________ _____________________________ OPERATION IN BOOSTER HEAT PUMP 6...

Страница 44: ...rtatore Commerciale Tecnico Postvendita Agenzia Logistica CED Ricambi CAT Descrizione prodotto reclamato Codice prodotto reclamato SCRIVERE MATRICOLA PRODOTTO O NUMERO FATTURA Data di ricezione reclam...

Страница 45: ...Consumatore disporre le attrezzature necessarie e sostenere i costi per la messa in sicurezza dei tecnici durante l intervento le eventuali avarie di trasporto graffi ammaccature e simili i danni da u...

Страница 46: ...46...

Страница 47: ...Direttiva CE sulle basse tensioni 2002 95 EC Linee guida UE per la limitazione delle sostanze dannose RoHS e dei rifiuti da apparecchiature elettriche ed elettroniche WEEE conforme alle disposizioni D...

Страница 48: ...itolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d A...

Отзывы: