Installer
_________________________________________________________
Designer
___________________________________________________________
Plant location
Street
______________________________________________________________________________________________________________________
N°
___________________
City
__________________________________________________________________
CAP
_______________
Province
___________________________________________
Installed System Mode
__________________________________________________________________
U.I. serial number
______________________________
Installation date
_____________________________________
EU freshmen
__________________________________________________________________________
________________________________________________________________________________
Plant type
Radiators
□
Summer cooling
□
Fan-Coil
□
DHW production
□
Radiant panels
□
Heating
□
Outdoor unit and indoor unit checklist YES NO VALUE
The outdoor unit is located outside the building
The outdoor unit is perfectly level on both axes
Presence of anti-vibration mounts between the outdoor unit and the ground or shelf
Check the safety distances indicated in the manual
Distance between indoor and outdoor unit (max 15m) attached
A
Difference in height between indoor and outdoor unit (max 5 m) attached
A
The pipes of the refrigeration lines (1/4 “- 3/8”) for HR 3.0 or (1/4 “- 5/8”) for HR 7.8
Folder tightness control
Check for any crushing of copper pipes
Control of the insulation of the refrigeration lines
The refrigeration lines were pressed with nitrogen at 40 bar for at least 12 h
The refrigeration system was put under vacuum
Condensate drain connection with suitable slope
The distances shown in the attachment have been respected
B
Electrical wiring check list
Adequate magnetothermic switch dedicated to the indoor unit
Distance between electrical contactor and indoor unit
Cable section Appropriate electric power supply
Connecting the room thermostat
The correct tightening of the electrical connections has been carried out
Electric power cable section between internal and external
Communication cable of the indoor and outdoor unit (3x1.0 mm²) (contacts C, 1.2)
Signal cable between indoor and outdoor (4x0.75mm² for PB3 and STC)
A suitable grounding has been performed
16. Checks for the HUB RADIATOR first start-up request
Содержание HUB RADIATOR MINI 11.0
Страница 27: ...27 7 2 WIRING DIAGRAM HUB RADIATOR MINI XL 6 0...
Страница 28: ...28 7 3 WIRING DIAGRAM HUB RADIATOR MINI XL 8 0...
Страница 29: ...29 7 4 WIRING DIAGRAM HUB RADIATOR MINI XL 11 0...
Страница 30: ...30 7 5 WIRING DIAGRAM HUB RADIATOR MINI XL 16 0...
Страница 31: ...31 Marrone Nero Blu 7 6 WIRING DIAGRAM HUB RADIATOR MINI XL 24 0...
Страница 46: ...46...