ATTENTION!

In fig. 5 shows an example of an inadmissible application, with a 

distance of 10 meters but with a difference in height of> 5 meters.

Fig. 5

6 m

4 m

3. OUTDOOR UNIT INSTALLATION

3.1  GENERAL INDICATIONS

When  choosing  the  installation  position,  carefully  observe  the 

following indications:

-   Make sure that the difference in height between the INDOOR

  UNIT and the UNIT OUTSIDE is not greater than 5.0 m.

-   The appliance must be installed so that the influences of

  adjacent structures and / or the effects of climatic conditions

  details (snow, wind etc ...), do not compromise the

  operation of the product and / or the safety of people and

  property.

-   Make sure that the space in the back of the unit is greater than

  30 cm. The front must have more than 60 cm. of space.

-   Make sure there are no obstacles to free movement

  of the air through the heat exchangers:

A) do not place plants or animals directly next to the flow

  of the air;

B) avoid installation in corners where it usually settles

  of dust, leaves and anything else that can reduce efficiency

  of the exchangers obstructing the passage of air (Fig 6).

Fig. 6

-  Avoid installation in bottlenecks and small shafts as acoustic

  reverberations could be favored.

  IInquire about any limits in noise emissions provided for the

  area of   the municipal territory in which it is installed the

  appliance. In case of doubts it is advisable to consult previously

  an acoustic technician, qualified for one impact assessment, in

  order to prevent disputes from third party.

-   Prevent the air expelled from the fans from penetrating

  through adjacent doors and / or windows, causing situations

  disturbing people.

-   Install the outdoor unit on a rigid base equipped with

  appropriate anti-vibration bearings to avoid the increase of

  vibrations e noise, so as not to disturb neighbors (Fig. 7).

Fig. 7

-   Position the air outlet so that the flow is not hindered in any

  way. In case of strong wind, make sure that the fan is working

  properly by positioning the unit longitudinally, along a wall or

  using a shield.

-   If the appliance is to be suspended from an external wall, the

  substrate must comply with the technical specifications. The

  wall where the unit must be installed, it must be brick or

  material of similar consistency, otherwise it must be Reinforced.

  The support brackets must be stable, resistant and with an

  adequate degree of protection against corrosion.

ATTENTION! 

Make sure of the load-bearing capacity of the part 

on which the shelves are placed and of the anchoring system 

to the wall itself, according to the weight of the appliance to be 

installed.

-  Do not install the appliance near heat sources and / or fire risk

  areas.

-   Installation in areas with a highly corrosive atmosphere not is

  allowed; in particular climatic conditions such as in proximity of

  the sea, it is mandatory to provide a duration of shorter life of

  the product and in any case a more frequent one ed

  careful maintenance.

-   In the outdoor unit, from which the water of condensation,

  provide a suitable drainage and / or channeling of the same, in

  order to avoid situations of danger due for example to the

  formation of ice on transit areas.

-   The outdoor unit is designed to be installed outdoors and it

  does not need a special base, however it must be positioned

  safely on a support surface horizontal with adequate load

  bearing capacity and equipped with suitable anti-vibration

  rubber pads.

3.2 CLEARANCE DISTANCES OUTDOOR UNIT (Fig. 8)

Respect the minimum spaces, so as to allow correct operation 

and all installation and maintenance operations.

Содержание HUB RADIATOR MINI 11.0

Страница 1: ...L Patented high efficiency direct coolant water exchange to produce domestic hot water and heating for small and medium sized users HUB RADIATOR MINI XL INSTALLATION MANUAL FIRST START UP MANDATORY FO...

Страница 2: ...n the last page The entry into force of new provisions or changes to those in force will not constitute a reason for any obligation of the A2B Accorroni E G S r l towards third parties The A2B Accorro...

Страница 3: ...B RADIATOR MINI XL 16 0 32 9 MINI XL RADIATOR HUB CIRCULATOR 33 10 DIVERTER VALVE HUB RADIATOR MINI XL 33 11 ELECTRIC RESISTANCE MINI XL 33 12 WARNINGS 33 12 1 Qualification of the installer 33 12 2 P...

Страница 4: ...nternal copper exchangers auxiliary back up and emergency supplementary resistor refrigerant gas connections DHW air siphon jolly valve safety valve filling cock pressure gauge diverter valve to give...

Страница 5: ...e outdoor unit 4 Remove the cover of the outdoor unit 5 Connect the terminal cables according to the numbers on the unit terminal block respecting the sections shown in table 1 6 Secure the cables so...

Страница 6: ...ple A of table 4 B INSTALLAZIONE CON LUNGHEZZAMINIMAAMMISSIBILE Qualora la distanza tra le unit Unit Interna ed Unit Esterna sia inferiore a 3 metri come in questo caso dove la lunghezza delle tubazio...

Страница 7: ...base equipped with appropriate anti vibration bearings to avoid the increase of vibrations e noise so as not to disturb neighbors Fig 7 Fig 7 Position the air outlet so that the flow is not hindered...

Страница 8: ...ing elements and moisture from the system Check that each pipe both the gas and liquid side pipes between the internal and external groups has been connected correctly and that all the wiring required...

Страница 9: ...quid side tap 3 7 PUMP DOWN This procedure is carried out when the unit needs to be moved or assistance is carried out on the refrigerant circuit Emptying allows all the refrigerant to be collected in...

Страница 10: ...irculator 4 Automatic filling group 5 Manual filling taps 6 System pressure gauges with 1 4 connections 7 Safety valve with 3 bar calibration and max pressure 10 bar 8 Diverter valve with 3 4 connecti...

Страница 11: ...em heat dispersion G Connect a special safety drain at the 1 2 female threaded connection of the safety valve H Make the electrical connections between the electrical panel and the main power supply a...

Страница 12: ...alve 4 Male threaded connection SAE cooling line 1 4 R410A Booster 1 5 Male threaded connection SAE cooling line R410A 5 8 or 3 8 Booster 1 6 Male threaded connection SAE cooling line 1 4 R410A Booste...

Страница 13: ...3 48 3 57 3 67 3 78 3 88 4 00 4 11 4 20 4 35 4 47 4 60 4 73 4 86 5 00 5 15 5 29 40 2 25 2 32 2 39 2 47 2 54 2 62 2 70 2 78 2 86 2 94 3 02 3 11 3 20 3 29 3 38 3 47 3 57 3 66 3 76 3 86 3 97 4 08 4 19 4...

Страница 14: ...3 18 3 28 3 37 3 47 3 62 3 67 3 77 3 88 3 99 4 14 4 25 4 36 4 50 4 62 4 74 4 87 5 02 5 15 40 2 18 2 25 2 33 2 40 2 47 2 55 2 62 2 70 2 78 2 86 2 94 3 02 3 10 3 19 3 28 3 37 3 46 3 56 3 65 3 75 3 86 3...

Страница 15: ...O P 1 Thermal power 2 Absorbed power 2 C O P 2 Thermal power 3 Absorbed power 3 C O P 3 Thermal power 4 Absorbed power 4 C O P 4 Thermal power 5 Absorbed power 5 C O P 5 Thermal power 6 Absorbed powe...

Страница 16: ...ANTI VIBRATION KIT FOR INSTALLATION ON SHELVES ANTI VIBRATION FLOOR BASE IN VULCANIZED RUBBER HEIGHT FROM THE GROUND MM 95 WITH LEVEL AND SCREWS FOR BOOSTER HR 3 0 7 8 9 0 COMPLETE STAINLESS STEEL SP...

Страница 17: ...dary display yellow color display configurable by parameter CF43 PB1 PB2 PB3 PB4 Set point from parameter Real set point Hysteresis RTC Machine status the display shows the chiller set when the unit i...

Страница 18: ...of parameters Parameter being edited increases its value Press and release from main view allows the display of the probe values configured temperatures pressures in the upper display and the label co...

Страница 19: ...zer the expected range Flashing icon generic alarm Code on display P4 Probe alarm Probe faulty our Activate output open Automatic PB4 resistive value collector rel alarm if the value is within out of...

Страница 20: ...l Booster Charging alarm thermostat 3 Q E thermostat connection 3 Replacement of the Q E contact open thermostat connection cable A12 Defrost End defrost 1 Lack of refrigerant gas 1 External Booster C...

Страница 21: ...escrizione min max udm Risoluzion e ST18 Set point ambiente in chiller ST20 ST21 C F dec int ST19 Differenziale ambiente in chiller 0 0 0 25 0 45 C F Dec int ST20 Set minimo ambiente in chiller 50 0 5...

Страница 22: ...ttivo contatto chiuso 1 Attivo contatto aperto 0 1 12 Allarme termica pompa acqua evaporatore termica ventilatore di mandata 13 Allarme termica pompa acqua condensatore 14 Flussostato condensatore 15...

Страница 23: ...Funzionamento continuo in uscita 4 20mA 4 Funzionamento su chiamata del compressore 4 20mA 0 4 CO12 Compressore 1 0 Abilitato 1 OFF 0 1 CO13 Compressore 2 parzializzazione 0 Abilitato 1 OFF 0 1 CO14...

Страница 24: ...abilitato 1 Abilitato 0 1 dF17 Ritardo allarme di minima all inversione della valvola 4 vie 0 250 Sec FA09 Massima velocit ventole in estate 30 100 FA10 Set temperatura pressione minima velocit vento...

Страница 25: ...el allarme uscita open collector 0 Uscita senza tensione in condizioni normali con tensione in presenza di allarme 1 Uscita con tensione in condizioni normali senza tensione in presenza di allarme 0 1...

Страница 26: ...Umin 80 T 8 s OK U Umin U Umax Before making connections make sure you have correctly sized the section of the power cables based on the actual distance from the counter Always provide for a special o...

Страница 27: ...27 7 2 WIRING DIAGRAM HUB RADIATOR MINI XL 6 0...

Страница 28: ...28 7 3 WIRING DIAGRAM HUB RADIATOR MINI XL 8 0...

Страница 29: ...29 7 4 WIRING DIAGRAM HUB RADIATOR MINI XL 11 0...

Страница 30: ...30 7 5 WIRING DIAGRAM HUB RADIATOR MINI XL 16 0...

Страница 31: ...31 Marrone Nero Blu 7 6 WIRING DIAGRAM HUB RADIATOR MINI XL 24 0...

Страница 32: ...ulation pump 30 Refrigeration line R410A 1 4 liquid 31 5 8 R410A refrigeration line gas 32 Base support as standard 6 7 8 9 24 18 10 11 17 16 13 15 14 1 30 30 31 31 1 5 22 23 23 32 2 29 2 3 25 26 28 3...

Страница 33: ...s are equipped with a motorized diverter valve with spring return The diverter valve is powered and automatically diverts to the system when the temperature of the technical storage exceeds 47 C param...

Страница 34: ...pipes Do not allow the power cables to come into contact with pipes Install zone motorized valves in the system to prevent the water contained in the accumulation not circulate freely when it is not...

Страница 35: ...at least 30 minutes 14 3 CLEANING THE CIRCUIT ATTENTION If the motor burns with perforation of the windings it is necessary to carefully clean the refrigerant circuit to avoid subsequent burns or bre...

Страница 36: ...r switching on and 16 for switching off ATTENTION In all cases described below in which the programmer gives consent to start the actual operation of the radiator is however also affected by the adjus...

Страница 37: ...el on both axes Presence of anti vibration mounts between the outdoor unit and the ground or shelf Check the safety distances indicated in the manual Distance between indoor and outdoor unit max 15m a...

Страница 38: ...______________________________________________________________________________ _________________________________________________________________________________________________________________________...

Страница 39: ...s INDOOR UNIT OUTDOOR UNIT Failure to comply with this application will result in the non ignition by the authorized assistance Attached A Attached B 6 m 4 m INDOOR UNIT OUTDOOR UNIT INSTALLATION NOT...

Страница 40: ...__________ ________________ _______________ ________________ ______________ ___________ ________________ POSITIONING THE OUTDOOR UNIT TO THE GROUND WALL A WINDOW ON BRACKETS ANTI VIBRATION SHELVES ROO...

Страница 41: ...rte superiore del compressore a circa 8 cm di distanza dalla calotta FUNZIONAMENTO IN POMPA DI CALORE BOOSTER 3 TEMPERATURA DI EVAPORAZIONE U E C Pb3 _______ TEMPERATURA ACQUA TECNICA C Pb1 _______ NB...

Страница 42: ...pe that comes out from the top of the compressor about 8 cm away from the hood OPERATION IN BOOSTER HEAT PUMP 3 EVAPORATION TEMPERATURE O U C Pb3 _______ TECHNICAL WATER TEMPERATURE C Pb1 _______ ATTE...

Страница 43: ...STOMER INSTALLER TECHNICAL ASSISTANCE CUSTOMER SIGNATURE SIGNATURE SIGNATURE _____________________________ _____________________________ _____________________________ OPERATION IN BOOSTER HEAT PUMP 6...

Страница 44: ...rtatore Commerciale Tecnico Postvendita Agenzia Logistica CED Ricambi CAT Descrizione prodotto reclamato Codice prodotto reclamato SCRIVERE MATRICOLA PRODOTTO O NUMERO FATTURA Data di ricezione reclam...

Страница 45: ...Consumatore disporre le attrezzature necessarie e sostenere i costi per la messa in sicurezza dei tecnici durante l intervento le eventuali avarie di trasporto graffi ammaccature e simili i danni da u...

Страница 46: ...46...

Страница 47: ...Direttiva CE sulle basse tensioni 2002 95 EC Linee guida UE per la limitazione delle sostanze dannose RoHS e dei rifiuti da apparecchiature elettriche ed elettroniche WEEE conforme alle disposizioni D...

Страница 48: ...itolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d A...

Отзывы: