12.2 PRELIMINARY INFORMATION

Before starting the installation, it is necessary to make sure that 

the planning phases and obtaining any necessary authorizations 

have been completed (for example: local authorities - Municipality, 

etc.), in addition to the appropriate technical checks (for example: 

evaluation of acoustic impact).

It is recommended in order to rely on a qualified heating engineer 

who  guarantees  the  correct  execution  of  the  aforementioned 

phases, whether they are optional or mandatory.

12.3 TRANSPORT AND HANDLING

The  device  is  shipped  on  wooden  pallets,  with  cardboard  and 

plastic  protections.  The  appliance  can  be  handled  by  suitably 

equipped personnel and with equipment suitable for the weight 

of  the  product,  such  as  a  forklift  or  transpallet,  taking  care  to 

distribute  the  weight  on  the  supports,  which  is  unbalanced 

towards the compressor (water connections side).

Any  lifting  by  means  of  belts  or  ropes  can  be  carried  out  by 

binding  the  ropes  to  two  sturdy  metal  pipes  inserted  in  the 

crossbars present under the base of the machine.

Ensure that the ropes are blocked at the points of anchorage to 

the pipes by means of suitable fasteners or safety pins; protect 

the contact points between the ropes and the appliance using 

cardboard or other suitable material.

Upon delivery, check that during transport no visible damage has 

occurred on the packaging and / or on the appliance. If damage 

is found, immediately file a formal complaint with the shipper. Do 

not install equipment damaged during transport.

It is forbidden to dispose of the packaging parts in the 

environment, or leave them within the reach of children as 

they are a potential source of danger.

12.4 USE OF THE INSTRUCTIONS

This manual is an integral part of the product and must be given 

to the owner of the appliance, so that he can keep it carefully for 

any future use or for consultation.

ATTENTION! When installing or working on the appliance, 

observe all the instructions contained in this manual and 

anything  else  applicable  to  the  product,  according  to 

national safety standards. Changes to connections of any 

kind and / or failure to comply with these instructions will 

result in the immediate forfeiture of the manufacturer’s 

warranty and liability.

12.5 GENERAL SYSTEM CHECKS

ATTENTION! Before filling the system, make sure that the 

pipes do not contain foreign material, such as sand, slag, 

rust flakes and so on, which could damage the exchanger. 

It is good practice to wash the system, by-passing the unit, 

before filling it.

Load the system, taking care to check the opening of the shut-off 

valves and the closure of the system drain cock.

ATTENTION!

-   Connect the indoor unit first and then the outdoor unit,

 

firmly fixing the pipes.

-   Make sure that the drain is not loose.

-   Make sure that the auxiliary lines are stay isolated.

-  Make sure that the drain drains properly.

 

Attach the drain to the other pipes.

-   Do not allow the power cables to come into contact

 

with pipes.

-  Install zone motorized valves in the system

 

to prevent the water contained in the accumulation not

 

circulate freely when it is not necessary, that is

 

when there is no consent from the thermoregulation.

13. START-UP

13.1 FIRST START-UP MODE

In order to activate the warranty conditions provided for by the 

regulations in force, it is mandatory to request the first ignition 

service  from  a  C.A.T.  A2B  Accorroni  E.G.  s.r.l.  authorized  by 

filling in the form shown.

The form must be sent by e-mail to [email protected]

13.2 FIRST START-UP CHECKS

Before  proceeding  with  the  commissioning  of  the  device,  it  is 

necessary to make sure that:

-  the safety conditions and all the provisions set out in

 

this manual has been complied with;

-  the fixing to the support surface is stable and the areas of

 

respect are free from any obstacle or material that prevent

 

easy accessibility to the device;

-   the hydraulic and electrical connections, with particular

 

attention to grounding, have been carried out correctly;

-   interception, loading, unloading and venting devices of the

 

plant are in the correct operating conditions and

 

have been properly checked.

ATTENTION! The start-up of the appliance, in conditions of 

non-compliance with the requirements of this manual and / 

or the regulations in force on safety and plant engineering, 

will result in the forfeiture of the warranty conditions.

13.3 START-UP

The  start-up  of  the  device  and  the  selection  of  the  operating 

mode can be performed by acting directly on the microprocessor 

keyboard with the “SUN” button.

Press and hold for at least 2/3 seconds, when released, the LED 

indicating the sun will begin to flash (compressor count).

After a few minutes the LED will become steady, and the machine 

will start operating, heating the technical water of the indoor unit 

up  to  the  SET-POINT  temperature.  At  this  point  the  machine 

enters full capacity and will carry out all the on and off cycles 

automatically and autonomously.

After  starting  the  device,  check  the  correct  functioning  of  the 

system, paying particular attention to the following:

- the water pump must not emit abnormal noise,

as this situation indicates that the air has not been purged

correctly or that the water flow rate is not sufficient

(possible obstructions, clogging or regulation of the

devices on the system);

-  the voltage measured in the power supply terminals must be

 

included in the 210-240 Volt range for models with single

 

phase power supply. Lower values   indicate one voltage drop

 

in the power line too high, with consequent possible damage

 

to the compressor, which can also occur also for voltages

 

greater than those indicated above;

-   the temperature difference measured between the inlet and

 

outlet of the device it must be between 3 ° C and 8 ° C; values  

 

less than 3 °C indicate an excessive flow of water, vice versa

 

the flow it will be too low with values   greater than 8 °C;

-   if the above conditions do not come realized, turn off the

 

machine and made corrective actions to allow the regular

 

operation of the system.

Содержание HUB RADIATOR MINI 11.0

Страница 1: ...L Patented high efficiency direct coolant water exchange to produce domestic hot water and heating for small and medium sized users HUB RADIATOR MINI XL INSTALLATION MANUAL FIRST START UP MANDATORY FO...

Страница 2: ...n the last page The entry into force of new provisions or changes to those in force will not constitute a reason for any obligation of the A2B Accorroni E G S r l towards third parties The A2B Accorro...

Страница 3: ...B RADIATOR MINI XL 16 0 32 9 MINI XL RADIATOR HUB CIRCULATOR 33 10 DIVERTER VALVE HUB RADIATOR MINI XL 33 11 ELECTRIC RESISTANCE MINI XL 33 12 WARNINGS 33 12 1 Qualification of the installer 33 12 2 P...

Страница 4: ...nternal copper exchangers auxiliary back up and emergency supplementary resistor refrigerant gas connections DHW air siphon jolly valve safety valve filling cock pressure gauge diverter valve to give...

Страница 5: ...e outdoor unit 4 Remove the cover of the outdoor unit 5 Connect the terminal cables according to the numbers on the unit terminal block respecting the sections shown in table 1 6 Secure the cables so...

Страница 6: ...ple A of table 4 B INSTALLAZIONE CON LUNGHEZZAMINIMAAMMISSIBILE Qualora la distanza tra le unit Unit Interna ed Unit Esterna sia inferiore a 3 metri come in questo caso dove la lunghezza delle tubazio...

Страница 7: ...base equipped with appropriate anti vibration bearings to avoid the increase of vibrations e noise so as not to disturb neighbors Fig 7 Fig 7 Position the air outlet so that the flow is not hindered...

Страница 8: ...ing elements and moisture from the system Check that each pipe both the gas and liquid side pipes between the internal and external groups has been connected correctly and that all the wiring required...

Страница 9: ...quid side tap 3 7 PUMP DOWN This procedure is carried out when the unit needs to be moved or assistance is carried out on the refrigerant circuit Emptying allows all the refrigerant to be collected in...

Страница 10: ...irculator 4 Automatic filling group 5 Manual filling taps 6 System pressure gauges with 1 4 connections 7 Safety valve with 3 bar calibration and max pressure 10 bar 8 Diverter valve with 3 4 connecti...

Страница 11: ...em heat dispersion G Connect a special safety drain at the 1 2 female threaded connection of the safety valve H Make the electrical connections between the electrical panel and the main power supply a...

Страница 12: ...alve 4 Male threaded connection SAE cooling line 1 4 R410A Booster 1 5 Male threaded connection SAE cooling line R410A 5 8 or 3 8 Booster 1 6 Male threaded connection SAE cooling line 1 4 R410A Booste...

Страница 13: ...3 48 3 57 3 67 3 78 3 88 4 00 4 11 4 20 4 35 4 47 4 60 4 73 4 86 5 00 5 15 5 29 40 2 25 2 32 2 39 2 47 2 54 2 62 2 70 2 78 2 86 2 94 3 02 3 11 3 20 3 29 3 38 3 47 3 57 3 66 3 76 3 86 3 97 4 08 4 19 4...

Страница 14: ...3 18 3 28 3 37 3 47 3 62 3 67 3 77 3 88 3 99 4 14 4 25 4 36 4 50 4 62 4 74 4 87 5 02 5 15 40 2 18 2 25 2 33 2 40 2 47 2 55 2 62 2 70 2 78 2 86 2 94 3 02 3 10 3 19 3 28 3 37 3 46 3 56 3 65 3 75 3 86 3...

Страница 15: ...O P 1 Thermal power 2 Absorbed power 2 C O P 2 Thermal power 3 Absorbed power 3 C O P 3 Thermal power 4 Absorbed power 4 C O P 4 Thermal power 5 Absorbed power 5 C O P 5 Thermal power 6 Absorbed powe...

Страница 16: ...ANTI VIBRATION KIT FOR INSTALLATION ON SHELVES ANTI VIBRATION FLOOR BASE IN VULCANIZED RUBBER HEIGHT FROM THE GROUND MM 95 WITH LEVEL AND SCREWS FOR BOOSTER HR 3 0 7 8 9 0 COMPLETE STAINLESS STEEL SP...

Страница 17: ...dary display yellow color display configurable by parameter CF43 PB1 PB2 PB3 PB4 Set point from parameter Real set point Hysteresis RTC Machine status the display shows the chiller set when the unit i...

Страница 18: ...of parameters Parameter being edited increases its value Press and release from main view allows the display of the probe values configured temperatures pressures in the upper display and the label co...

Страница 19: ...zer the expected range Flashing icon generic alarm Code on display P4 Probe alarm Probe faulty our Activate output open Automatic PB4 resistive value collector rel alarm if the value is within out of...

Страница 20: ...l Booster Charging alarm thermostat 3 Q E thermostat connection 3 Replacement of the Q E contact open thermostat connection cable A12 Defrost End defrost 1 Lack of refrigerant gas 1 External Booster C...

Страница 21: ...escrizione min max udm Risoluzion e ST18 Set point ambiente in chiller ST20 ST21 C F dec int ST19 Differenziale ambiente in chiller 0 0 0 25 0 45 C F Dec int ST20 Set minimo ambiente in chiller 50 0 5...

Страница 22: ...ttivo contatto chiuso 1 Attivo contatto aperto 0 1 12 Allarme termica pompa acqua evaporatore termica ventilatore di mandata 13 Allarme termica pompa acqua condensatore 14 Flussostato condensatore 15...

Страница 23: ...Funzionamento continuo in uscita 4 20mA 4 Funzionamento su chiamata del compressore 4 20mA 0 4 CO12 Compressore 1 0 Abilitato 1 OFF 0 1 CO13 Compressore 2 parzializzazione 0 Abilitato 1 OFF 0 1 CO14...

Страница 24: ...abilitato 1 Abilitato 0 1 dF17 Ritardo allarme di minima all inversione della valvola 4 vie 0 250 Sec FA09 Massima velocit ventole in estate 30 100 FA10 Set temperatura pressione minima velocit vento...

Страница 25: ...el allarme uscita open collector 0 Uscita senza tensione in condizioni normali con tensione in presenza di allarme 1 Uscita con tensione in condizioni normali senza tensione in presenza di allarme 0 1...

Страница 26: ...Umin 80 T 8 s OK U Umin U Umax Before making connections make sure you have correctly sized the section of the power cables based on the actual distance from the counter Always provide for a special o...

Страница 27: ...27 7 2 WIRING DIAGRAM HUB RADIATOR MINI XL 6 0...

Страница 28: ...28 7 3 WIRING DIAGRAM HUB RADIATOR MINI XL 8 0...

Страница 29: ...29 7 4 WIRING DIAGRAM HUB RADIATOR MINI XL 11 0...

Страница 30: ...30 7 5 WIRING DIAGRAM HUB RADIATOR MINI XL 16 0...

Страница 31: ...31 Marrone Nero Blu 7 6 WIRING DIAGRAM HUB RADIATOR MINI XL 24 0...

Страница 32: ...ulation pump 30 Refrigeration line R410A 1 4 liquid 31 5 8 R410A refrigeration line gas 32 Base support as standard 6 7 8 9 24 18 10 11 17 16 13 15 14 1 30 30 31 31 1 5 22 23 23 32 2 29 2 3 25 26 28 3...

Страница 33: ...s are equipped with a motorized diverter valve with spring return The diverter valve is powered and automatically diverts to the system when the temperature of the technical storage exceeds 47 C param...

Страница 34: ...pipes Do not allow the power cables to come into contact with pipes Install zone motorized valves in the system to prevent the water contained in the accumulation not circulate freely when it is not...

Страница 35: ...at least 30 minutes 14 3 CLEANING THE CIRCUIT ATTENTION If the motor burns with perforation of the windings it is necessary to carefully clean the refrigerant circuit to avoid subsequent burns or bre...

Страница 36: ...r switching on and 16 for switching off ATTENTION In all cases described below in which the programmer gives consent to start the actual operation of the radiator is however also affected by the adjus...

Страница 37: ...el on both axes Presence of anti vibration mounts between the outdoor unit and the ground or shelf Check the safety distances indicated in the manual Distance between indoor and outdoor unit max 15m a...

Страница 38: ...______________________________________________________________________________ _________________________________________________________________________________________________________________________...

Страница 39: ...s INDOOR UNIT OUTDOOR UNIT Failure to comply with this application will result in the non ignition by the authorized assistance Attached A Attached B 6 m 4 m INDOOR UNIT OUTDOOR UNIT INSTALLATION NOT...

Страница 40: ...__________ ________________ _______________ ________________ ______________ ___________ ________________ POSITIONING THE OUTDOOR UNIT TO THE GROUND WALL A WINDOW ON BRACKETS ANTI VIBRATION SHELVES ROO...

Страница 41: ...rte superiore del compressore a circa 8 cm di distanza dalla calotta FUNZIONAMENTO IN POMPA DI CALORE BOOSTER 3 TEMPERATURA DI EVAPORAZIONE U E C Pb3 _______ TEMPERATURA ACQUA TECNICA C Pb1 _______ NB...

Страница 42: ...pe that comes out from the top of the compressor about 8 cm away from the hood OPERATION IN BOOSTER HEAT PUMP 3 EVAPORATION TEMPERATURE O U C Pb3 _______ TECHNICAL WATER TEMPERATURE C Pb1 _______ ATTE...

Страница 43: ...STOMER INSTALLER TECHNICAL ASSISTANCE CUSTOMER SIGNATURE SIGNATURE SIGNATURE _____________________________ _____________________________ _____________________________ OPERATION IN BOOSTER HEAT PUMP 6...

Страница 44: ...rtatore Commerciale Tecnico Postvendita Agenzia Logistica CED Ricambi CAT Descrizione prodotto reclamato Codice prodotto reclamato SCRIVERE MATRICOLA PRODOTTO O NUMERO FATTURA Data di ricezione reclam...

Страница 45: ...Consumatore disporre le attrezzature necessarie e sostenere i costi per la messa in sicurezza dei tecnici durante l intervento le eventuali avarie di trasporto graffi ammaccature e simili i danni da u...

Страница 46: ...46...

Страница 47: ...Direttiva CE sulle basse tensioni 2002 95 EC Linee guida UE per la limitazione delle sostanze dannose RoHS e dei rifiuti da apparecchiature elettriche ed elettroniche WEEE conforme alle disposizioni D...

Страница 48: ...itolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d A...

Отзывы: