![Abus SECVEST Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/abus/secvest/secvest_installer-manual_3682217079.webp)
Configuration
79
Name/function
Explanation
Exit Mode,
cont.
Internally arming the partition
•
The user must first start the arming sequence using the user code, proximity
keyfob or remote control.
The alarm panel then sounds the exit tone and saves the start time in the
log book.
If the "Final Door" zone is open, the alarm panel emits a continuous exit tone.
The exit tone sounds until the user:
a) closes the last exit door and then
b) locks the door and therefore activates the lock switch contact.
After the lock switch contact is activated, the partition is internally armed once
the settle time has expired.
The "Final Door" zone is also converted into a "Normal Alarm" zone.
The alarm panel saves the activation of the "Lock Set" zone in the log book.
Disarming the partition
•
The user unlocks the door and therefore activates the lock switch contact.
The "Lock Set" zone is opened. The alarm panel saves the activation of the
"Lock Set" zone in the log book. The original "Final Door" zone which was
converted into a "Normal Alarm" zone is switched back into a "Final Door" zone.
The entry time starts when the door is opened. The entry tone sounding at this
point is different from a normal entry tone.
•
If the user locks the door again without starting the entry time, the alarm panel
remains armed and the "Final Door" zone is converted again into a "Normal
Alarm" zone. The alarm panel stops the warning tone.
•
To comply with BS8243, "After Entry" must be set to "Never" in order to prevent
confirmation.
Exit Terminate
Internally arming the partition
•
The user must first start the arming sequence. Then the user ends the arming
process after existing the monitoring area.
•
The user can start the arming sequence using the user code, proximity keyfob
or remote control. (Note: arming with remote control must not be set to "Instant",
Installer Mode->System->User Access->Remote Inst. Set).
•
The user ends arming by activating a zone with type "Exit Terminate"
(see explanation of zone types).
•
Note that the exit time is unlimited with this option, i.e. the alarm panel waits until
it receives the signal to end the arming process before it arms. The alarm panel
emits the exit tone during this time. The alarm panel saves the start time of
arming (and not the arming itself) in the log book. The partition is armed after the
settle time has expired.
Содержание SECVEST
Страница 1: ...I n s t a l l e r m a n u a l...
Страница 3: ...Contents 3...
Страница 12: ...Device overview 12 International key assignment...
Страница 14: ...Device overview 14...
Страница 28: ......
Страница 114: ...Configuration 114 ARC Reporting Phone Book Name function Explanation checkbox Tel Recipient Name of the recipient...
Страница 143: ...Configuration 143 Contacts Up to 12 recipients can be defined here to whom messages are sent...
Страница 169: ...Index 169...
Страница 170: ...Index 170...
Страница 171: ...ABUS wireless alarm system Secvest Manufacturer ABUS Security Center GmbH Co KG Linker Kreuthweg 5 86444 Affing Germany...