preparatIons, InstallatIon and takIng Into operatIon
9
• A parking spot must also be planned for in front of the wallbox so that the vehicle
can at all times be reached with the integrated or with an external charging cable.
• The recommended installation height is 120 to 140 cm
from the floor to the lower edge of the housing. This
recommendation may be adjusted upwards or down-
wards depending on local conditions.
• Sufficient air circulation must be ensured at the installa-
tion site so that the wallbox is cooled during operation:
Always observe the allowed operating temperatures
(see “Technical specifications” on page 23).
• The mounting area must have an even surface that pro-
vides sufficient stability for installing the wallbox.
• The required mounting area for the ABL Wallbox is at
least 512 x 429 mm (H x W). All of the mounting plate
of the wallbox must be in contact with the mounting
surface.
• To ensure the safe operation of the wallbox, minimum
clearances of 50 cm must be kept on all sides of the
housing.
• In general, the ABL Wallbox is engineered for operation in high ambient tempera-
tures. However, it must be ensured that the maximum operating temperature is not
exceeded through external influences such as direct sunlight or similar.
• The wallbox meets the requirements for outdoor installation. Outdoors, the wallbox
should only be installed in covered locations that provide sufficient protection from
weather-related pollution.
Requirements for the power supply
The following standards must always be considered for the electrical installation of the
ABL Wallbox:
• All regulatory requirements for low voltage installations according to IEC 60364-1
and IEC 60364-5-52 apply.
• ABL Wallboxes are designed for connection to and operation on rated voltages of
230 V (phase-neutral) or 400 V (phase-phase) at 50 Hz.
• The installation site must offer a sufficiently dimensioned power supply according to
HD 60364-7-722:2012 (see also “Guidelines & Norms” on page 27): This power
supply must be reserved exclusively for the wallbox and must not be used to supply
other electrical devices.
• If necessary, a separate power supply must be installed that is intended exclusively
for connecting the wallbox and complies with the general requirements for cabling
and building infrastructure.
120 to
140 cm