6.1 Alarms
Message
Fault
Action
Locked, Alarm LED on
Lock input activated
Unlock
Switch not in AUTO
mode, Alarm LED on
Slide switch is in handle
or lock position
Turn slide switch into
the AUTO position
Phases crossed
Phase rotation of sources 1
and 2 are different
Connect the phases of both sources in
the same order
S1 undervoltage
Voltage of source 1 is under the
threshold level set in parameter
“Dropout voltage, lower threshold“
Check the correlation between power
source and device configuration
S1 overvoltage
Voltage of source 1 is over the
threshold level set in parameter
“Dropout voltage, upper threshold“
Check the correlation between power
source and device configuration
S1 phase missing
One or two phases of
source 1 are missing
Check the power source
and connections
S1 unbalance
Phases of source 1 are not symmetric
Check the power source
S1 phase rotation
Phase rotation of source 1 is
different from the value of
parameter “Phase sequence“
Connect the phases according to the
configuration
S1 invalid frequency
Frequency of source 1 is out of range
set in parameters “Drop-out frequency,
upper threshold“ and “Drop-out
frequency, lower threshold“
Check the correlation between power
source and device configuration
S2 undervoltage
Voltage of source 2 is under the
threshold level set in parameter
“Dropout voltage, lower threshold“
Check the correlation between power
source and device configuration
Table 6.1 Alarms-list in level 3 and 4, LCD and touch control interfaces
LCD
Touch
—
6. Troubleshooting
L
CD
, T
O
U
CH
Warning
Any troubleshooting should be conducted by
trained and authorized personnel only.
Appropriate personal protectiveequipment
(PPE) shall be used when troubleshooting the
ATS panel.
Hazardous voltage may be present. Discon
-
nect all power sources before performing
work inside the ATS panel.
Failure to do so may result in serious injury
or death.
Содержание Zenith ZTG 30
Страница 2: ......
Страница 6: ...6 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Страница 10: ...10 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Страница 52: ...52 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 91: ...91 1 Fig 7 3 ZTGD delayed transition circuit diagram ...
Страница 93: ...93 1 Figure A Figure B ...
Страница 94: ...94 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE Figure C ...
Страница 96: ...2 96 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 108: ...2 108 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 114: ...2 114 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...