background image

Introduction

The Sure-Set Current Switch (SSC) Series 

of digital output switches are noninva-

sive devices designed to detect current 

flowing through a cable or wire. A cost 

effective solution for monitoring on and 

off status or proof of operation, these 

devices are ideal for monitoring the cur-

rent load on motors driving fans, pumps, 

chillers, compressors and blowers. The 

Model SSC Current Switch has a univer-

sal power supply. Excitation is magneti-

cally induced from the current carrying 

conductor (wire or cable) being sensed, 

making these devices completely self-

powered.

Warning: Risk of Electric Shock

Disconnect power supply before mak-

ing electrical connections. Contact 

with components carrying hazardous 

voltage can cause electrical shock and 

may result in severe personal injury or 

death.

Warning: Risk of Arc-Flash

Disconnect power supply before mak-

ing electrical connections. Contact 

with components carrying hazardous 

voltage can cause electric shock and 

may result in severe personal injury or 

death.

Setup and Adjustments

T

he Sure-Set Model SSC series of switches 

employ a unique method to set the oper-

ating set point of the device. The Sure-Set 

Current Switch is designed to allow the 

installer to select the operating setpoint 

prior to opening the electrical enclosure.

Since the Sure-Set does not require cali-

bration on a powered and operating load, 

the safety hazards and Personal Protec-

tive Equipment (PPE) required for protec-

tion against Arc-Flash are not necessary! 

In fact, the installer or site engineer can 

pre-set all Sure-Set Current Switches used 

for a particular installation prior to deliver-

ing the parts to the job site. The installer 

selects the proper Sure-Set model for 

the application (230 VAC or 480 VAC) and 

verifies the Motor HP for the system to be 

monitored.

Select Operating Range

1.  Verify the motor Full Load HP for the 

system to be monitored.

2.  Verify the motor operating voltage.
3.  Verify that the proper Sure-Set model 

was selected to monitor the motor 

used in the system. (Sure-Set Current 

Switches are available for 230 VAC 

and 480 VAC motors both in standard 

low and high HP ranges.)

4.  Set the Sure-Set operating setpoint 

to the motor Full Load HP by rotating 

the range selector switch on top of 

the Sure-Set to the proper motor HP 

(see Fig. 2). The Sure-Set operating 

setpoint is  now set to properly moni-

tor the motor operation. No calibra-

tion on a live load is necessary.

65 (2-9/16)

69 (2-23/32)

27 (1-1/16)

Fig. 1 Model SSC

Dimensions

mm(in.)

Model SSC-2S/SSC-2H/SSC-4S/SSC-4H

Operation and Installation Instructions

!

!

Fig. 2 HP Range Selector

Отзывы: