Ze nit h Z TG S e r i e s AT S ,
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
Continued on the next page
Parameters
(continued)
*Default
Device Parameters (continued)
Time Delays (continued)
Transfer from
S2 to S1
0...120 min
(2* s)
S1 priority: How long the device waits before
transfer sequence back to available S1 begins.
This delay is overridden by 'Override S2 Failure'
in case of S2 failure.
S2 priority: How long the device is keeping the
load on failed S2 although S1 is already
available.
Pre-transfer
S2 to S1
0*...300 s
Enabled only when any digital output is
configured as 'Pre-transfer Signal'.
How long the device is keeping pre-transfer
signal activated before transferring from S2
to S1.
Post-transfer
S2 to S1
0*...300 s
Enabled only when any digital output is
configured as 'Pre-transfer Signal'.
How long the device is keeping pre-transfer
signal activated after transferring from S2
to S1.
Generator Stop
0...60 min
(5* min)
Enabled only when generator is in use.
Generator cooling time, how long the device is
keeping the generator running without load
after returning to priority source.
Load Shed
0*...60 s
Enabled only when any digital output is
configured as 'Load Shed'.
How long before the transfer from priority to
non-priority source the device activates load
shed signal.
Elevator Pre-signal
S1 to S2
0*...60 s
Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated before transferring from
S1 to S2.
Elevator Post-
signal S1 to S2
0*...60 s
Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated after transferring from
S1 to S2.
Elevator Pre-signal
S2 to S1
0*...60 s
Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated before transferring from
S2 to S1.
Elevator Post-
signal S2 to S1
0*...60 s
Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated after transferring from
S2 to S1.
Содержание Zenith ZTG 30
Страница 2: ......
Страница 6: ...6 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Страница 10: ...10 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Страница 52: ...52 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 91: ...91 1 Fig 7 3 ZTGD delayed transition circuit diagram ...
Страница 93: ...93 1 Figure A Figure B ...
Страница 94: ...94 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE Figure C ...
Страница 96: ...2 96 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 108: ...2 108 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 114: ...2 114 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...